Hitachi L200 Marine Battery User Manual


 
L200 Inverter
Operations
and Monitoring
4–17
Set Second Motor
If you assign the [SET] function to an intelligent input terminal, you can select between
two sets of motor parameters. The second parameters store an alternate set of motor
characteristics. When the terminal [SET] is turned ON, the inverter will use the second
set of parameters to generate the frequency output to the motor. When changing the state
of the [SET] input terminal, the change will not take effect until the inverter is stopped.
When you turn ON the [SET] input, the inverter operates per the second set of parame-
ters. When the terminal is turned OFF, the output function returns to the original settings
(first set of motor parameters). Refer to
Configuring the Inverter for Multiple Motors
on page 4–56 for details.
Option
Code
Terminal
Symbol
Function Name
Input
State
Description
08 SET Set (select) 2nd
Motor Data
ON causes the inverter to use the 2nd set of motor
parameters for generating the frequency output
to motor
OFF causes the inverter to use the 1st (main) set of
motor parameters for generating the frequency
output to motor
Valid for inputs:
C001, C002, C003, C004,
C005
Required settings:
(none)
Notes:
If the terminal state is changed while the inverter is
running, the inverter continues using the current set
of parameters until the inverter is stopped.
Example (requires input configuration—see
page 3–42
):
See I/O specs on page 4–6
.
SET
12345L
PCS