Hitachi L200 Marine Battery User Manual


 
L200 Inverter
Appendix B
B–11
When a read coil is outside the defined coils, the final coil data to be transmitted
contains “0“as the status of the coil outside the range.
When the Read Coil Status command cannot be executed normally, see the exception
response.
Read Holding Register [03h]:
This function reads the contents of the specified number of consecutive holding registers
(of specified register addresses). An example follows below.
Reading previous three trip factors from an inverter having a slave address “5”
This example assumes the previous three trip factors are as follows:
L200 Command D081 (N) D082 (N-1) D083 (N-2)
Coil Number 0019h 001Ah 0018h
Trip factor Over-voltage (E07) Under-voltage (E09) No trip
Query:
Note 1: Broadcasting is disabled.
.Response:
Note 2: Data is transferred by the
specified number of data bytes
(data size). In this case, 6 bytes
are used to return the content
of three holding registers.
No. Field Name
Example
(Hex)
1 Slave address *1 05
2 Function code 03
3 Register start number
(high order)
00
4 Register start number
(low order)
19
5 Number of holding
registers (high order)
00
6 Number of holding
registers (low order)
03
7 CRC-16 (high order) D5
8 CRC-16 (low order) 88
No. Field Name
Example
(Hex)
1 Slave address 05
2 Function code 03
3 Data size (in bytes) *2 06
4 Register start number
(high order)
00
5 Register start number
(low order)
07
6 Register start number + 1
(high order)
00
7 Register start number +1
(low order)
09
8 Register start number + 2
(high order)
00
9 Register start number +2
(low order)
FF
10 CRC-16 (high order) 36
11 CRC-16 (low order) 37