Hitachi SJ700 Marine Battery User Manual


 
*1: The protection method conforms to JIS C 0920 (IEC60529)
*2: The applicable motor refers to Hitachi standard 3-phase motor (4-pole).To use other motors, be sure to prevent the rated motor current (50Hz) from exceeding the rated output current of the inverter.
*3: The output voltage decreases as the main power supply voltage decreases except for the use of AVR function.
*4: Braking resistor is not integrated in the inverter. Please install optional braking resistor or dynamic braking unit when large braking torque is required.
*5: Conforms to the test method specified in JIS C 60068-2-6 2010 IEC 60068-2-6 2007).
*6: To operate the motor beyond 50/60Hz, please consult with the motor manufacturer about the maximum allowable rotation speed.
*7: Storage temperature refers to the temperature in transportation.
*8: The frequency command is the maximum frequency at 9.8V for input voltage 0 to 10VDC, or at 19.8mA for input current 4 to 20mA.
If this characteristic is not satisfactory for your application,contact your Hitachi representative.
STANDARD SPECIFICATIONS
SJ700B Series
Series Name
Applicable Motor Capacity 004: 0.4kW (1/2HP)
|
4000:400kW (500HP)
Power Source
Available
0.4
(1/2)
Applicable Motor kW (HP)
0.75
(1)
1.5
(2)
2.2
(3)
3.7
(5)
4.0
(5)
5.5
(7.5)
7.5
(7.5)
11
(15)
15
(20)
18.5
(25)
22
(30)
30
(40)
37
(50)
45
(60)
55
(75)
75
(100)
90
(125)
110
(150)
132
(175)
150
(200)
160
(220)
185
(250)
220
(300)
315
(400)
400
(550)
SJ700D/SJ700 series
Model Name Indication
Model Configuration
3-phase 400V
3-phase 200V
L : 3-phase 200V class
H : 3-phase 400V class
F : With keypad
U : US version
E : European version
Note : Japanese version
F : Integrated EMC filter
Version
Series Name
Applicable Motor Capacity 055: 5.5kW (7.5HP)
|
1600:160kW (220HP)
Power Source
SJ700B series
L : 3-phase 200V class
H : 3-phase 400V class
F : With keypad
U : US version
Note : Asia version
F : Integrated EMC filter
3-phase 200V
3-phase 400V
SJ700D
SJ700B
3-phase 400V
*
1
*
1
SJ700
3-phase 400V
*1 Available only for Asia version and US Version. without EMC Filter
300HFF
300HFUF
30(40)
39.4
47.3
57
63
20
14(30.8)
370HFF
370HFUF
37(50)
48.4
58.1
70
77
22(48.4)
Built-in BRD circuit (optional resistor)
5.9m/s
2
(0.6G), 10-55Hz
3-phase 400V class
Model SJ700B-
Enclosure (*1)
Applicable motor (4-pole, kW(HP)) (*2)
Output Ratings
Input Rating
Braking
Vibration (*5)
EMC filter
Zero-phase Reactor
Weight (lbs.)
Asia Version
US Version
IP20 IP00
Rated capacity
(kVA)
Rated output current (A)
Overload capacity (output current)
Rated output voltage (*3)
Rated input voltage (V)
Rated input current (A)
Dynamic braking (Short-time) (*4)
0LQLPXPYDOXHRIUHVLVWRUї
400V
480V
External dynamic braking unit (option)
-
2.9m/s
2
(0.3G), 10-55Hz
110HFF
110HFUF
11(15)
15.2
18.2
22
24
35
6(13.2)
075HFF
075HFUF
7.5(10)
11
13.3
16
18
70
6(13.2)
055HF
055HFU
5.5(75)
9.7
11.6
14
17
70
-
-
3.5(7.7)
150HFF
150HFUF
15(20)
20.0
24.1
29
32
35
6(13.2)
185HFF
185HFUF
18.5(25)
25.6
30.7
37
41
24
14(30.8)
220HFF
220HFUF
22(30)
29.7
35.7
43
47
24
14(30.8)
450HFF
450HFUF
45(60)
58.8
70.6
85
94
30(66)
550HFF
550HFUF
55(75)
72.7
87.2
105
116
30(66)
750HFF
750HFUF
75(100)
93.5
112.2
135
149
30(66)
900HFF
900HFUF
90(125)
110.8
133
160
176
55(121)
1100HFF
1100HFUF
110(150)
135.1
162.1
195
199
55(121)
1320HFF
1320HFUF
132(150)
159.3
191.2
230
253
70(154)
1600HFF
1600HFUF
160(220)
200.9
241.1
290
300
70(154)
Built-in BRD circuit (optional resistor)
3-phase 200V class
Model SJ700B-
Enclosure (*1)
Applicable motor (4-pole, kW (HP)) (*2)
Output Ratings
Input Rating
Braking
Vibration (*5)
EMC filter
Zero-phase Reactor
Weight (lbs.)
US Version
IP20
120%,60sec
3-phase (3-wire) 200 to 240V (corresponding to input voltage)
3-phase 200 to 240V +10%, -15%, 50/60Hz±5%
Built-in (EN61800-3 category C3)
Built-in
200V
240V
Rated capacity
(kVA)
Rated output current (A)
Overload capacity (output current)
Rated output voltage (*3)
Rated input voltage (V)
Rated input current (A)
Dynamic braking (Short-time) (*4)
0LQLPXPYDOXHRIUHVLVWRUї
External dynamic braking unit (option)
-
2.9m/s
2
(0.3G), 10-55Hz
110LFUF
11(15)
15.2
18.2
44
48
10
6(13.2)
150LFUF
15(20)
20.0
24.1
58
64
10
6(13.2)
185LFUF
18.5(25)
25.2
30.3
73
80
7.5
14(30.8)
220LFUF
22(30)
29.4
35.3
85
94
7.5
14(30.8)
300LFUF
30(40)
39.1
46.9
113
120
7.5
14(30.8)
370LFUF
37(50)
48.4
58.1
140
150
22(48.4)
450LFUF
45(60)
58.5
70.2
169
186
30(66)
550LFUF
55(75)
72.7
87.2
210
240
30(66)
750LFUF
75(100)
93.5
112.2
270
280
43(94.6)
5.9m/s
2
(0.6G), 10-55Hz
120%,60sec
3-phase (3-wire) 380 to 480V (corresponding to input voltage)
3-phase 380 to 480V +10%, -15%, 50/60Hz±5%
Built-in (EN61800-3 category C3)
Built-in
HFUF
LFUF
LFUF3
HFEF3
HFUF3
HFF3
LFF3
HFF
HF2
HFE2
HFU2
8