Hitachi SJ700B Marine Battery User Manual


 
A GROUP: STANDARD FUNCTIONS
= Allowed
= Not permitted
Code Function Name Monitored data or setting
Default Setting
Setting
during
operation
(allowed or not)
Change
during
operation
(allowed or not)
SJ700/SJ700D(CTmode)
SJ700B
-FE -FU -F -F -FU
Basic settings
A001
Frequency source setting
00 (keypad potentiometer) (*1), 01 (control circuit terminal block),
02 (digital operator), 03 (RS485), 04 (option 1), 05 (option 2),
06 (pulse-string input), 07 (easy sequence), 10 (operation function result)
01 01 02 01 02
A002
Run command source setting
01 (control circuit terminal block), 02 (digital operator), 03 (RS485), 04 (option 1), 05 (option 2)
01 01 02 01 02
A003
Base frequency setting
30. to "maximum frequency " (Hz)
50. 60. 60. 50. 60.
A203
Base frequency setting, 2nd motor
30. to "maximum frequency, 2nd motor" (Hz)
50. 60. 60. 50. 60.
A303
Base frequency setting, 3rd motor
30. to "maximum frequency, 3rd motor" (Hz)
50. 60. 60. 50. 60.
A004
Maximum frequency setting
"base frequency" to 400. (Hz) (*2)
50. 60. 60. 50. 60.
A204
Maximum frequency setting, 2nd motor
"base frequency, 2nd motor" to 400. (Hz) (*2)
50. 60. 60. 50. 60.
A304
Maximum frequency setting, 3rd motor
"base frequency, 3rd motor" to 400. (Hz) (*2)
50. 60. 60. 50. 60.
Analog input and others
A005
[AT] selection
00 (switching between O and OI terminals), 01 (switching between O and O2
terminals), 02 (switching between O terminal and keypad potentiometer) (*1), 03
(switching between OI terminal and keypad potentiometer) (*1), 04 (switching
between O2 and keypad potentiometer) (*1)
00 00 00 00 00
A006
[O2] selection
00 (single), 01 (auxiliary frequency input via O and OI terminals) (nonreversible),
02 (auxiliary frequency input via O and OI terminals) (reversible), 03 (disabling
O2 terminal)
03 03 03 03 03
A011
O-L input active range start frequency
0.00 to 99.99, 100.0 to 400.0 (Hz) (*4)
0.00 0.00 0.00 0.00 0.00
A012
O-L input active range end frequency
0.00 to 99.99, 100.0 to 400.0 (Hz) (*4)
0.00 0.00 0.00 0.00 0.00
A013
O-L input active range start voltabe
0. to "[O]-[L] input active range end voltage" (%)
0. 0. 0. 0. 0.
A014
O-L input active range end voltabe
"[O]-[L] input active range start voltage" to 100. (%)
100. 100. 100. 100. 100.
A015
O-L input active range start frequency selection
00 (external start frequency), 01 (0 Hz)
01 01 01 01 01
A016
External frequency lter time constant
1. to 30. or 31. (500 ms lter ±0.1 Hz with hysteresis)
31. 31. 31. 31. 31.
A017
Easy sequence function selection
00 (disabling), 01 (enabling)
SJ700D: 00 (disabling), 01 (PRG terminal), 02 (always on)
00 00 00 00 00
Multispeed operation and Jogging
A019
Multispeed operation selection
00 (binary: 16 speeds selectable with 4 terminals), 01 (bit: 8 speeds selectable with 7 terminals)
00 00 00 00 00
A020
Multispeed frequency setting
0.00 or “start frequency” to “maximum frequency” (Hz)
0.00 0.00 0.00 0.00 0.00
A220
Multispeed frequency setting, 2nd motor
0.00 or “start frequency” to “maximum frequency, 2nd motor” (Hz)
0.00 0.00 0.00 0.00 0.00
A320
Multispeed frequency setting, 3rd motor
0.00 or “start frequency” to “maximum frequency, 3rd motor” (Hz)
0.00 0.00 0.00 0.00 0.00
A021
-
A035
Multispeed 1-15 setting
0.00 or “start frequency” to “n-th maximum frequency” (Hz)
0.00 0.00 0.00 0.00 0.00
A038
Jog frequency setting
"Start frequency" to 9.99 (Hz)
1.00 1.00 1.00 1.00 1.00
A039
Jog stop mode
00 (free-running after jogging stops [disabled during operation]), 01 (deceleration
and stop after jogging stops [disabled during operation]), 02 (DC braking after
jogging stops [disabled during operation]), 03 (free-running after jogging stops
[enabled during operation]), 04 (deceleration and stop after jogging stops [enabled
during operation]), 05 (DC braking after jogging stops [enabled during operation])
00 00 00 00 00
V/f Characteristic
A041
Torque boost method selection
00 (Manual torque boost) / 01 (Automatic torque boost)
00 00 00 00 00
A241
Torque boost method selection, 2nd motor
00 (Manual torque boost) / 01 (Automatic torque boost)
00 00 00 00 00
A042
Manual torque boost value
0.0 to 20.0 (%)
1.0 1.0 1.0 1.0 1.0
A242
Manual torque boost value, 2nd motor
0.0 to 20.0 (%)
1.0 1.0 1.0 1.0 1.0
A342
Manual torque boost value, 3rd motor
0.0 to 20.0 (%)
1.0 1.0 1.0 1.0 1.0
A043
Manual torque boost frequency adjustment
0.0 to 50.0 (%)
5.0 5.0 5.0 5.0 5.0
A243
Manual torque boost frequency adjustment, 2nd motor
0.0 to 50.0 (%)
5.0 5.0 5.0 5.0 5.0
A343
Manual torque boost frequency adjustment, 3rd motor
0.0 to 50.0 (%)
5.0 5.0 5.0 5.0 5.0
A044
V/F characteristic curve selection,
1st motor (*5)
00 (VC), 01 (VP), 02 (free V/f), 03 (sensorless vector control),
04 (0Hz-range sensorless vector), 05 (vector with sensor)
00 00 00 00 00
A244
V/F characteristic curve selection,
2nd motor (*5)
00 (VC), 01 (VP), 02 (free V/f), 03 (sensorless vector control),
04 (0Hz-range sensorless vector)
00 00 00 00 00
A344
V/F characteristic curve selection, 3rd motor
00 (VC), 01 (VP)
00 00 00 00 00
A045
V/f gain setting
20. to 100. (%)
100. 100. 100. 100. 100.
A046
Voltage compensation gain setting
for automatic torque boost. 1st motor
0. to 255.
100. 100. 100. 100. 100.
A246
Voltage compensation gain setting
for automatic torque boost, 2nd motor
0. to 255.
100. 100. 100. 100. 100.
A047
Slippage compensation gain setting
for automatic torque boost, 1st motor
0. to 255.
100. 100. 100. 100. 100.
A247
Slippage compensation gain setting
for automatic torque boost, 2nd motor
0. to 255.
100. 100. 100. 100. 100.
DC Braking
A051
DC braking enable
00 (disabling), 01 (enabling), 02 (set frequency only)
00 00 00 00 00
A052
DC braking frequency setting
0.00 to 99.99, 100.0 to 400.0 (Hz) (*4)
0.50 0.50 0.50 0.50 0.50
A053
DC braking wait time
0.0 to 5.0 (s)
0.0 0.0 0.0 0.0 0.0
A054
DC braking force during deceleration
SJ700/SJ700D (CT): 0. to 100. (%) <75 to 132kW:0. to 80./185kW and over:0. to 35.>
SJ700D (VT): 0. to 70. (%) <75 to 132kW:0. to 50.>
SJ700B: 0. to 70. (%) <90kW and over:0. to 50.>
0 0 0 0 20.0
A055
DC braking time for deceleration
0.0 to 60.0 (s)
0.0 0.0 0.0 0.0 0.5
A056
DC braking/edge or level detection for [DB] input
00 (edge operation), 01 (level operation)
01 01 01 01 01
A057
DC braking force for starting
SJ700/SJ700D (CT): 0. to 100. (%) <75 to 132kW:0. to 80./185kW and over:0. to 35.>
SJ700D (VT): 0. to 70. (%) <75 to 132kW:0. to 50.>
SJ700B: 0. to 70. (%) <90kW and over:0. to 50.>
0. 0. 0. 0. 0.
A058
DC braking time for starting
0.0 to 60.0 (s)
0.0 0.0 0.0 0.0 0.0
A059
DC braking carrier frequency setting
SJ700/SJ700D (CT): 0.5 to 15.0(kHz) <75 to 132kW:0.5 to 10.0/185kW and over:0.5 to 3.0>
SJ700D (VT): 0.5 to
12.0 (kHz)
<75 to 132kW:0.5 to 8.0>
SJ700B: 0.5 to 12.0 (kHz) <90kW and over:0.5 to 8.0>
5.0
<75 to 132kW:3.0>
3.0 3.0
(*1) This setting is valid only when the OPE-SR is connected. (*2) 4000HF:30. to 120. (Hz)
(*3) Derating is applied for SJ700B. Please consult technician at Hitachi or its distributor before use. (*4) 4000HF:0.00 to 99.99,100.0 to 120.0 (Hz)
(*5) SJ700D (VTmode):00 (VC), 01 (VP), 02 (free V/F), 03 (sensorless vector control)
15