Honeywell YP7999A1000 Marine Instruments User Manual


 
YP7999A1000 CONTROLINKS™ FUEL AIR RATIO CONTROL PANEL
3 66-2060—01
TROUBLESHOOTING
System Diagnostics
The S7999D touchscreen interface indicates the current fault and keeps a fault history log. The R7999 ControLinks control and
the ML7999A Universal Parallel-Positioning Actuator also have LED fault blink codes. Refer to the appropriate product instruction
sheet for further troubleshooting information and diagnostic codes.
FIELD WIRING
Table 1. Field Wiring and Terminal Designation
1
.
Terminal #
To Connecting
Device Description
1
2
L1 Panel power 120Vac Power Supply, 3A Max.
L1 power to circuit breaker.
Provide disconnect means and overload protection as required.
2 L2 Panel neutral
GND Panel ground
4
3
L1 L1 customer convenience wire point – provided for 4 actuators – 120Vac, 50/60Hz
2
3
L2 L2 customer convenience wire point – provided for 4 actuators
GND
3
Panel ground GND customer convenience wire point – provided for 4 actuators
9 HFP High Fire Proven output from ControLinks controller to burner control
10 LFP Low Fire Proven output from ControLinks controller to burner control
11 HF High Fire drive command input from burner controller
12 MV Main Valve command input from burner controller
13 LF Low Fire drive command input from burner controller
14 LCI Limit Control Input from burner limit string, including on/off control, LWCO, high-limit, etc…
15 LCO Limit Control Output from ControLinks controller to burner control demand/interlock inputs
200
3,4
DR1 Air Actuator DR1 command input
201
3,4
DR2 Air Actuator DR2 command input
202
3,4
CW Air Actuator potentiometer CW output
203
3,4
S Air Actuator potentiometer S output
204
3,4
CCW Air Actuator potentiometer CCW output
GND
3,4
Ground Air Actuator ground
205
3,4
DR1 Fuel 1 Actuator DR1 command input
206
3,4
DR2 Fuel 1 Actuator DR2 command input
207
3,4
CW Fuel 1 Actuator potentiometer CW output
208
3,4
S Fuel 1 Actuator potentiometer S output
209
3,4
CCW Fuel 1 Actuator potentiometer CCW output
GND
3,4
Ground Fuel 1 Actuator ground
210
3,4
DR1 Fuel 2 Actuator DR1 command input
211
3,4
DR2 Fuel 2 Actuator DR2 command input
212
3,4
CW Fuel 2 Actuator potentiometer CW output
213
3,4
S Fuel 2 Actuator potentiometer S output
214
3,4
CCW Fuel 2 Actuator potentiometer CCW output
GND
3,4
Ground Fuel 2 Actuator ground