FLR Flow Transmitter
Installation & Programming Instructions
Page 12
Zero Capture
The zero position of the meter cone must be set when
installing the meter. To capture the zero calibration
position, press ENTER at the ZERO CAP prompt. NO
will display. Press either arrow key to change to YES,
then press ENTER to capture zero.
Meter Type
The meter can be programmed to compensate for
specific gravity, pressure, and temperature depending
upon the application. Its displayed name is METER-
TYP and is viewed or changed using the List Item
Selection Procedure found on page 8.
Note: Refer to Flow Chart on pages 10 and 11. When
Meter Type WATER is selected, specific gravity
(SP GRAV) will automatically follow.
Note: Refer to Flow Chart on pages 10 and 11. When
Meter Type OIL is selected, meter size (METERSIZ),
viscosity (VISC SUS), and specific gravity (SP GRAV)
will automatically follow.
Note: Refer to Flow Chart on pages 10 and 11. When
Meter Type GAS is selected, operating pressure (OP
PRESS ), operating temperature (OP TEMP), and
specific gravity (SP GRAV) will automatically follow.
Meter Size
Meter size is used in conjunction with Viscosity to
perform viscosity correction. Table 3 lists the available
selection choices. Its displayed name is METERSIZ
and is viewed or changed using the List Item Selection
Procedure found on page 8.
Viscosity
Viscosity is used in conjunction with the Meter Size to
perform viscosity correction when the Meter type
selected is OIL. Enter in SUS units the viscosity of the
oil that will be used. Its displayed name is VISC SUS
and is viewed or changed using the Numeric Value
Entry Procedure found on page 8.
Operating Pressure
The operating pressure is used in gas applications to
compensate for the actual pressure being measured
at the meter. Enter the operating pressure in PSI units.
Its displayed name is OP PRES and is viewed or
changed using the Numeric Value Entry Procedure
found on page 8.
Operating Temperature
The operating temperature is used in gas applications
to compensate for the actual temperature of the gas
being measured at the meter. Enter the operating
temperature in ºF units. Its displayed name is OP
TEMP and is viewed or changed using the Numeric
Value Entry Procedure found on page 8.
Specific Gravity Correction Factor
Specific Gravity is used to compensate for the specific
gravity of the liquid or gas being measured with the
meter. Its displayed name is SP GRAV and is viewed
or changed using the Numeric Value Entry Procedure
found on page 8.
Damping
The Damping factor is increased to enhance the
stability of the flow readings. Damping values are
decreased to allow the flow meter to react faster to
changing values of flow.This parameter can range
from 0 to 99; factory default is 0. Its displayed name is
DAMPING and is viewed or changed using the
Numeric Value Entry Procedure found on page 8.
1
/
4
" &
1
/
2
"
meter
1
1
/
4
" & 1
1
/
2
"
meter
3
/
4
" &
1
"
meter
1GPM 30GPM2GPM
2GPM 50GPM5GPM
5GPM 75GPM10GPM
10GPM
100GPM20GPM
15GPM 150GPM30GPM
Table 3 - Meter Size Types