PowerLogic™ PM5500 series user manual Chapter 2—Hardware reference
HRB1684301-01 27
Specifications
The information contained in this section is subject to change without notice. See your
product’s technical datasheet at www.schneider-electric.com for the most current and
complete specifications.
For installation and wiring information, refer to the meter installation sheet.
Related topics
• See “MID compliance” on page 143 for specifications relevant to the Measuring
Instruments Directive (MID).
Mechanical
Electrical
Mechanical characteristics
Integrated display
model
(PM5560, PM5561)
IP degree of protection
(IEC 60529)
Front display: IP52
Meter body: IP30 (except connectors)
Connectors: IP20 with terminal covers installed, IP10
without terminal covers.
IP rating Front display: UL Type 12
Panel thickness 6.0 mm (0.25 in) maximum
Gasket thickness 1.0 mm (0.04 in)
Mounting position Vertical
Display type Monochrome graphics LCD, 128 x 128 resolution
Display backlight White LED
Viewable area 67 x 62.5 mm (2.64 x 2.46 in)
Keypad 4 button
Front panel LED indicators
Green LED (heartbeat / communications activity)
Amber LED (active alarm indicator or energy pulse output)
DIN rail mount model
(PM5563)
IP degree of protection
(IEC 60529)
Meter body: IP30 (except connectors)
Connectors: IP20 with terminal covers installed, IP10
without terminal covers.
Mounting position 35 mm DIN rail
LED indicators (top)
Amber LED (active alarm indicator / energy pulsing
Green LED (heartbeat / communications activity)
Electrical characteristics
Type of measurement
True RMS up to the 63rd harmonic on three-phase (3P,
3P + N)
128 samples per cycle, zero blind
Measurement
accuracy
IEC 61557-12 PMD/[SD|SS]/K70/0.2
Active energy
±0.2%
Class 0.2S, as per IEC 62053-22
Reactive energy
±2%
Class 2, as per IEC 62053-23
Active power ±0.2% as per IEC 61557-12
Reactive power ±1% as per IEC 61557-12
Apparent power ±0.5% as per IEC 61557-12
Current (5 A nominal, per
phase)
±0.15%
Voltage (L-N) ±0.1%
Frequency ±0.05%