19Part No. 550-100-068/0308
Multiple Steam Boiler Piping Gravity Condensate Return
Connect steam boiler piping
(continued)
Pipe as shown for gravity return systems, connect-A
ing point A to the wet gravity return.
For pumped-return systems, install boiler water •
level control on each boiler with body mark at
level indicated in Figure 42, page 28. Provide at
point A either:
Separate feed pumps and check valves for each •
boiler, or . . .
Single feed pump, with separate solenoid valve •
for each boiler.
For pumped-return systems, install a combination
B
oat and thermostatic trap on each boiler to prevent
ooding of one boiler while other boiler is firing.
Install trap in skim tapping (see Figure 39, page 27).
Connect traps to condensate receiver.
Gravity-return systems are self-levelling if the wet
returns are piped to the common system wet return.
Install boiler piping as shown in the preceding pages C
of this manual.
Install stop valves per ASME code requirements.D
For pump-return systems, if using automatic •
steam valves, use only slow-opening automatic
valves. Use a Weil-McLain Boiler Control Sys-
tem (such as a BCP panel) to open each steam
valve automatically before firing burner.
Construct common supply drop header with pipe
E
size at least same size as largest boiler header size.
Use:
F
A Weil-McLain Boiler Control System (such as •
a BCP panel) with header-mounted pressure
control(s) to sequence boilers, or . . .
A steam pressure controller.•
Install drip line in common supply drop header.
G
Gravity-return: Pipe drip line to wet return.•
Pumped-return: Use combination oat and •
thermostatic trap and drain to condensate
receiver.
See page 18 for numbered
circle references.