Part number 550-110-282/1108
26
GOLD
CGs-4E Gas-Fired Water Boiler — Boiler Manual
Field wiring6
Thermostat
1. Connectthermostatasshownonwiringdiagram
on boiler.
2.
Install on inside wall away from influences of
drafts, hot or cold water pipes, lighting fixtures,
television, sunrays, or fireplaces.
3. If thermostat has a heat anticipator, set heat antici-
pator in thermostat to match power requirements
of equipment connected to it. If connected directly
to boiler, set for 0.4 amps. For other devices, refer
to manufacturer’s specifications. Wiring diagram
on boiler gives setting for control module and gas
valve.Alsoseeinstructionswiththermostat.
Junction Box (continued)
1. Connect 120VACpower wiringasshownin
Figure 15.
2. Fused disconnect or service switch (15 amp. recom-
mended) may be mounted on this box. For those
installations with local codes which prohibit installa-
tion of fused disconnect or service switch on boiler,
install a 2 x 4 cover plate on the boiler junction box
and mount the service switch remotely as required
by the code.
For your safety, turn off electrical power supply at
service entrance panel before making any electrical
connections
to avoid possible electric shock hazard.
Failure to do so can cause severe personal injury or
death.
Wiring must be N.E.C. Class 1.
If original wiring as supplied with boiler must be re-
placed, use only type 105°C wire or equivalent.
Boilermustbe
electrically grounded as required by
NationalElectricalCodeANSI/NFPA70–latestedi-
tion.
Electrical installation must
comply with:
1. NationalElectricalCodeandanyothernational,
state, provincial or local codes or regulations.
2. InCanada,CSAC22.1CanadianElectricalCode
Part 1, and any local codes.
Wiring connections
Boilerisshippedwithcontrolscompletelywired.
Figure 15
Field wiring connections —
service switch and thermostat
(or end switch)
provided by installer
TheCGs-4Econtrolmoduleispolarity-sensitive.Thehotandneutralwiresmustbeconnected
tothecorrectleads.AashingPOWER lightusuallyindicatesreversedpolarityof120VAClead
wires.