Catalog Numbering Guide
FDBAES LED XX X X
Series:
FDBAES: Zone 1, 2, 21 and 22
ATEX / IEC Certified
SL - Space Lighting
E - Escape Route Lighting
Options:
A - Addressable
W - With Switch
(main supply and remote)
Lamp Type:
LED
Cable Entry:
N - NPT 3/4"
M - Metric M20
Optimum operating temperature for battery is 23 °F/-5 °C to 86 °F/+30 °C.
Lighting
Lighting: increased safety/fLameproof — BuLkhead
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© November 2011
A1346
Applications
• Providesadequatelightingand/orvisualindicationofaccesson
exitroutesduringanevacuationinahazardousenvironment.
• CanbeinstalledinhazardousareasdesignatedasZone1,2,21
and22.
• Typicalapplicationsincludeoilreneries,petrochemicalplants,
pulpandpapermills.
Features
• Allversions:
—Powersupply230Vac50/60Hz.
—1hourduration(emergency).
—ThreadedaccesscoverwithO-ringseal.
—Canbemaintainedinhazardousareasasaninternalswitch
cutsoffbatterysupplyautomaticallyoncethecoveris
unscrewedandopened.
—Batterypack.
—Escaperoutelighting:2.4V-1.5Ah(2cells-Nicd).
Spacelighting:7.2V-2.2Ah(6cells-NiMh)-Flameproof.
—Padlockableswitchisavailableonswitchedmodelswhich
individuallycutsoffpowersupplyandremotecontrol.
—Chargeindicatorby1greenLED(lifetimeover10years).
—Operatesinanyposition.
—Connectiontoplug-interminalblockvia2x5x2.5mm
2
terminals.
—Suppliedwithtwoxinglugs.
—Automaticbuilt-inself-testsystem(SATI)withmemorization
oftestsindicatedbyLEDs.
— Using a microprocessor and an internal clock, the unit will
carryoutautomatictests.
—Weeklytest:Lampcheckduring6seconds.
— Quarterly test: Emergency operation and lamp check for 1
hour.
— Can be remotely controlled and checked without switching
the mains off with remote control unit from Legrand (Catalog
Number 03901) or URA (Catalog Number 095448 and
095450)manufacturers.
— The remote control unit installed in a safe area or inside a
ameproofboxallowsmanualignitionofalltheunits(max.
300units)forvisualinspectionoftheiroperation.
—Escaperoutelighting:55lumens,0.50wattage.
Spacelighting:540lumens,0.95wattage.
• Addressableversions:
—Providingtheregulatorycontroloftheemergencylighting
unitsandcentralizinginformationcomingfromthoseunitson
acomputerizedmanagementsystem.
— Operating without any special line, communication between
unitsandthecontrolsystemisrealizedviamains-borne
signalsontheremotecontrolline.
— Capacity: one control system for 200 emergency lighting
units.
—Max.capacity:1000emergencylightingunitswithboosters.
Standard Materials
• Endcapsandcover:anti-corrosivegraypaintedZamak
• O-ringseal:Nitrile
• Lens:sealedtemperedglass
• Fixingbrackets:zincplatedsteelor316stainlesssteel
• Accessories:whitepaintedgalvanizedsteel
• Guard:zincplatedsteel
Options
• Addressablemonitoringsoftware,pleaseconsultfactory.
• Lowtemperatureapplication,pleaseconsultfactory.
Certifications and Compliances
• CerticationType:FLd
• Zone1-2
— Conforming to ATEX 94/9/CE: CE 0081 II2G
— ATEX/IEC Protection: Ex d IIC
— T Rating: T6
• Zone21-22
— Conforming to ATEX 94/9/CE: CE 0081 II 2 D
— ATEX/IEC Protection: Ex tD A21
— Surface Temperature: T176 °F/ T80 °C
• AmbientTemperature:-40°F/-40 °C to 131 °F/55 °C
• CEDeclarationofConformity:50203
• ATEXCerticate:LCIE97/ATEX6012
• IECExCerticate:IECExLCI04.0018
• OtherCertications:GOST
• IndexofProtection(solidandliquid):IP66/68
• ImpactResistance(shock):IK08
• InternalVolume:
> 122 in³/2 dm
3
(2 liters)
• Ex Standards EN / IEC 60079-0; 60079-1; 61241-0; 61241-1
• ProductStandards:EN/IEC60598-1;60598-2-22-NFC71800;
71820
• CEMStandards:EN/IEC55015;61547
• OtherStandards:EN/IEC60529(IP);62262(IK)
FDBAES LED Series Self-Contained Emergency Lighting Units
Flameproof
Zone 1 and 2 - 21 and 22
II 2 GD
ATEX / IECEx
IP66/68 - IK08
FDBAESLEDEM