Battery-Biz 5150 Marine Battery User Manual


 
NEG
POS
DC Input 10V-15VDC
Up to 200Amps Continuous
AC Output 110V - 120VAC 60Hz
Up to 18.2 Amps Continuous
P/N: 05200
TruePower2000(12V)
2000 Watts Continuous
4000 Watts Peak
NEG
POS
1500 Watts Continuous
3000 Watts Peak
DC Input 10V-15VDC
Up to 150Amps Continuous
AC Output 110V - 120VAC 60 Hz
12.5 Amps Continuous
P/N: 05150
TruePower1500
GFCI 110 VAC Output
Power Over TempOver Load
On
Off
0
100
%
100
%
0
DC
Input Voltage
Inverter
Output Current
On Board
Solutions
A ProMariner Company
Deluxe Inverter Remote
PowerFault
GFCI 110 VAC Output
PowerFault
Remote Port
GFCI PROTECTED 110 VAC Output
Power
Over Temp
Over Load
On
Off
On Board
Solutions
A ProMariner Company
4
Overview
TruePower Overview
The above picture outlines the front of the TruePower Inverter with bullets pointing out digital
bar graph display, on/off switch, led locations etc. Please Reference Table below for features:
1. ON/Off Switch turns the inverter to ON, OFF
2. Power light illuminates when inverter is on.
3. Fault Light illuminates Red for fault conditions such as over temperature, output
overload, or battery low voltage.
4. Two GFCI Protected AC Outputs to power connected appliances, Reset and Test
monthly capabilities.
5. Ventilation Openings provide air circulation for peak performance.
(front and rear panel)
6. Remote Port for optional simple remote with on / off switch and power and fault led
7. Main Breaker
8. Outlet Breaker
9. Terminal Strip
No AC output voltage. Red Fault LED light is illuminated.
Possible Cause:
- Inverter may be overloaded.
Solution:
- Disconnect all appliances connected to the inverter and reset the inverter by
turning the ON/Off switch to Off then back to ON.
Possible Cause:
- Battery voltage may be too high.
Solution:
-The inverter will restart if the battery voltage drops below 15.5 volts DC.
Possible Cause:
- Battery voltage may be too low.
Solution:
- Battery voltage becoming low, recharge battery and resume inverting power.
Possible Cause:
- Over temperature.
Solution:
- Allow the inverter to cool down. The inverter will start automatically.
Possible Cause:
- Unit may be defective
Solution:
- Call Factory Service 800 number.
No AC output voltage. NO Lights are illuminated.
Possible Cause:
- Battery voltage is too low.
Solution:
- Recharge the batteries. Restart the inverter with recharged batteries.
Possible Cause:
- Poor DC wiring.
Solution:
- Turn the inverter to Off. Disconnect the DC wiring. Use proper wiring and ensure
all connections are secure.
15
Troubleshooting
The picture outlines the back of the TruePower
Inverter with bullets pointing out DC connections,
fuse holder locations etc. The Table below references
the above numbered features of the back panel
10. DC Input Cable (Positive +)
11. DC Input Cable (Negative -)
12. Fan Housings
13. Ground Stud
14. Mounting flanges (Side)
15. Tech Spec Label
1
6
4
4