Cooper Lighting HR87C Marine Safety Devices User Manual


 
Sure-Lites • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • TEL 770.486.4800 • FAX 770.486.4801
08/23/2010 10:54:20 AM
Specifications and Dimensions subject to change without notice.
ADX041293
ELECTRICAL RATINGS
PHOTOMETRICS
TECHNICAL DATA
SERIES
CHICAGO HR 6-VOLT
Model Type DC Voltage 1 1/2 Hours Lamp Watts Remote Watts
HR87C SLC 6 87 24 63
HR117C SLC 6 117 24 93
HR12117C SLC 12 117 24 93
HR180C SLC 6 180 24 156
HR12170C SLC 12 170 24 146
HR12210C SLC 12 210 24 186
HR12360C SLC 12 360 24 336
Rated Wattage to 87 1/2% of Rated D.C. Voltage
Lamp Information
Type Wattage Number Figure
Halogen 12 29-66 1
Halogen 12 29-66 1
Halogen 12 29-45 1
Halogen 12 29-66 2
Halogen 12 29-45 2
Halogen 12 29-45 2
Halogen 12 29-45 2
*Batteries may be shipped separately. SLC=Sealed Lead Calcium
Horizontal Distribution
Vertical Distribution
Lamp No. 29-45 and 29-66
Initial Lumens
– 302
Lamp No. 29-45 and 29-66
15
FEET
LEFT
FEET
RIGHT
15
FEET FROM LAMP (Measured on axis)
0
1FC
LAMP
AXIS
15
FEET
LEFT
FEET
RIGHT
15
FEET FROM LAMP (Measured on axis)
0
LAMP
AXIS
0.
5 0.3 0.2
1FC
0 20 30 40 50 60
0 20 30 40 50 60
0.1
0.5 0.3 0.2 0.1
Heads
All metal formed aluminum
lampheads. The die cast metal
three dimensional swivel
assembly permits approximate
aiming adjustment from 80°
vertical and 358° rotation. The
placement is secured with a
lockable pivot mounted on a
rotating base ring.
Lamps
Designed specifically for
emergency lighting applications,
the PAR 36 sealed beam type
design insures optimum glare-
free light distribution along
with horizontal and vertical
adjustment by rotating the lens
within the housing. Tungsten
halogen lamps maximize light
output with lower wattage.
Housing
The rugged 18-gauge die-
formed steel housing is finished
with an attractive white
corrosion-resistant polyester
powder coat paint. Cabinet has
keyhole mounting slots,
universal mounting pattern,
and knockouts in rear and side
for AC/DC wiring connections
and accessory cord set. Up to
three lighting heads can be
mounted on the cabinet.
Line-Latched
Sure-Lites’ line-latched
electronic circuitry makes
installation easy and
economical. A labor efficient
AC-activated load switch
prevents the lamps from turning
on during installation to
a non-energized AC circuit.
Line-latching eliminates the
need for a contractor’s return
to a job site to connect the
batteries when the building’s
main power is permanently
turned on.
Solid-State Charger
Supplied with a 120/277 VAC,
voltage regulated solid-state
charger. Immediately upon
restoration of AC current after
a power failure, the charger
provides a high charge rate.
The charge circuit reacts to the
condition of the battery and
alters the rate of charge in
order to maintain peak battery
capacity and maximize battery
life. Solid-state construction
recharges the battery following
a power failure in accordance
with UL 924.
Overload and Short
Circuit Protectio
n
The solid-state overload
monitoring device in the DC
circuit disconnects the lamp
load from the battery should
excessive wattage demands be
made and automatically resets
when the overload or short
circuit is removed. This
overload current protective
feature eliminates the need
for fuses or circuit breakers
for the DC load.
Brownout Circuit
The brownout circuit in Sure-
Lites’ units monitors the flow
of AC current to the unit and
activates the emergency
lighting system when a
predetermined reduction
of AC power occurs. This
dip in voltage will cause most
ballasted fixtures to extinguish
causing loss of normal lighting
even though a total power
failure has not occurred.
Solid-State Transfer
The unit incorporates a solid-
state switching transistor which
eliminates corroded and pitted
contacts or mechanical failures
associated with relays. The
switching circuit is designed to
detect a loss of AC voltage and
automatically energizes the
lamps. Upon restoration of
the AC power, the emergency
lamps will switch off and the
charger will automatically
recharge the battery.
Low-Voltage Disconnect
When the battery’s terminal
voltage falls below 80% of the
rated voltage, the low-voltage
circuitry disconnects the
lighting load. The disconnect
remains in effect until normal
utility power is restored,
preventing deep battery
discharge.
Test Switch/Power Indicator
Ligh
t
Conveniently located Test
Switch allows for manual
verification of proper operation
of the transfer circuit and
emergency lamps. The Power
Indicator Light provides visual
assurance that the AC power
is on.
Sealed Lead Calcium Battery
The fully sealed, long-life,
maintenance-free lead calcium
battery is ideal for emergency
lighting applications. These
recombinant cycle batteries
typically provide eight to ten
years of life and may be
operated in any position.
Warranty
All Sure-Lites’ units are backed
by a firm one-year warranty
against defect in material and
workmanship (excluding
lamps). Maintenance free,
long-life, sealed lead calcium
batteries carry a five-year
pro-rata warranty.