Quick Installation Guide
00825-0100-4801, Rev KB
December 2010
Rosemount 3051S
9
STEP 4 CONTINUED...
Signal Wiring Grounding
Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical
equipment. Grounding terminations are provided on the sensor module and inside the Terminal
Compartment. These grounds are used when transient protect terminal blocks are installed or to
fulfill local regulations. See Step 2 below for more information on how the cable shield should be
grounded.
1. Remove the Field Terminals housing cover.
2. Connect the wiring pair and ground as indicated in Figure 7.
a. The cable shield should:
• Be trimmed close and insulated from touching the transmitter housing.
• Continuously connect to the termination point.
• Be connected to a good earth ground at the power supply end.
Figure 7. Wiring
3. Replace the housing cover. It is recommended that the cover be tightened until there is no
gap between the cover and the housing.
4. Plug and seal unused conduit connections.
DP
Trim shield and
insulate
Insulate
Shield
Connect Shield Back to the
Power Supply Ground
Ground for
Transient
Protection
Minimize
Distance
Minimize
Distance