TROUBLE/ INDICATION POSSIBLE CAUSE SUGGESTED REMEDY
Low battery alarm Bad connection or wiring Tighten all DC
sounds continuously connections
Low battery Low battery voltage Recharge battery.
alarm sounds Remove load from
inverter while recharging
battery
Motorized power tool Excessive start-up load If appliance does not start,
won’t start then appliance is drawing
excessive wattage and will
not work with inverter
Motorized power tool Purely inductive load Make the load not purely
does not operate at inductive. Operate an
correct speed incandescent lamp at
same time as motor
Television/Radio Snow in picture, buzz Keep inverter and
interference in speaker antenna distant from
each other. Use shielded
antenna cable. Connect
antenna to amplifier
9. FUSE REPLACEMENT
If external fuses blow, (or breakers trip), then there is a short or overload
in the DC wiring. Find and fix the problem before replacing the fuses
(or resetting the breaker). After fuse replacement, reconnect the inverter.
This power inverter is equipped with multiple internal fuses. Normally,
these fuses will not blow unless there is a serious problem inside the unit.
Internal fuses are replaceable, however, only electronically knowledgeable
people should attempt fuse replacement. If the unit is damaged during fuse
replacement, the warranty may be voided. Husky recommends contacting
Technical Support for guidance. Based on experience, it is best to return
the unit to Husky for repair. Husky Technical Support can be reached
by calling 954-584-4446, extension 19.