42 PowerMonitor 1000 Unit
Rockwell Automation Publication 1408-IN001E-EN-P - September 2013
Magnitude and Phase Angle
The power monitor continually returns voltage and current magnitude and phase angle data.
This data may be used to construct a phasor diagram, and in addition to the diagnostics
parameters, to troubleshoot wiring issues. The following exceptions apply.
Magnitude data is not returned by models 1408-EM1 and -EM2
Current phase angle 2 always returns 0 in open-delta wiring mode
Phase angles are consistent with the four-quadrant power metering diagram.
Refer to Power Metering on page 50.
Setup
Basic analog setup is required. In addition, a system power factor should be selected. The ranges
are as follows:
Low (52…95% lag, default setting)
High (85 lag …98% lead)
Leading (97 lag …89% lead)
Results
Wiring diagnostics results may be viewed using the following methods:
Web interface
LCD screen
Communication
HyperTerminal communication tool
Commands
Perform wiring diagnostics
Test wiring connections (LCD screen menu)
TIP
The Troubleshooting mode of the power monitor lets you view magnitude data.
Please refer to Troubleshooting Mode
on page 43.