PART 7: SECTION 2.2
GASEOUS SYSTEMS
40 July 2008
Macron Safety Systems (UK) Ltd
Burlingham House, Hewett Road, Gapton Hall Industrial Estate, Great Yarmouth, Norfolk NR31 0NN UK
Tel: +44 (0)1493 417600 Fax: +44 (0)1493 417700
E-mail: macron.info@tycoint.com Website: www.macron-safety.com
Hygood Sapphire™
Product Name Risk Design
Concentration
Comments LPCB Ref.
No.
Hygood
Sapphire™
Class A Standard (Solid fires, e.g.
paper, wood, plastics)
6.3% Design concentration includes 30%
safety factor
587Bb/01
Class A Cables (Solid fire risks
including cables)
6.1% Confirmation that minimum safety
factor is adequate
Class B (Liquid fires e.g. heptane) 6.4% Design concentration includes 30%
safety factor
Design concentration Class A Standard and Class B = Extinguishing concentration x safety factor (minimum 1.3).
Design concentration Class A Cables System test concentration. Where this value is lower than the Class A Standard value, the
Class A Standard value should be used for design purposes.
Design concentrations are as tested to LPS 1230 in BRE Test Report Number 208832 v2.
Extinguishing concentrations are as tested in BRE Test Report Number 208831 (ISO 14520-1 tests)
This system uses:
Design, Installation, Maintenance and User Manual: Hygood Novec
TM
1230 Total Flooding Systems (Engineered & Pre-engineered)
Design Manual Reference 14a-06H Issue 2
Software Programme: Novec 1230 FlowCalc Version 3.60
a) This system is suitable for storage in environmental conditions from -20° to +50°.
b) System pressure is specified as 24.8 bar @ 2C
Nitin Fire Protection Industries Ltd (NITIE)
501 Delta, Technology Street, Hirandani Gardens, Powai, Mumbai 400 076, India
Tel: +91 22 40457000 Fax: +91 22 66920910
E-mail: systems@nitinfire.com Website: www.nitinfire.com
Certificate No: 855c
Nitin ‘Nitin22725 bar HFC 227ea Gaseous Fire Suppression System
Product
Name
Risk Design
Concentration
Comments LPCB Ref.
No.
Nitin227 Class A Standard (Solid fires e.g.
paper, wood, plastics
7.8% Design concentration includes 30%
safety factor
855c/01
Class A Cables (Solid fires risks
including cables
- System not LPS1230 approved for risks
including cables
Class B (Liquid Fires e.g.heptane) 9.2% Design concentration includes 30%
safety factor
Design concentration Class A Standard and Class B = Extinguishing concentration x safety factor (minimum 1.3).
Design concentrations are as tested to LPS 1230 in BRE Test Report Number 231870
Extinguishing concentrations are as tested in BRE Test Report Number 231870 (ISO 14520-1 tests).
This system uses:
Design Manual: ‘Nitin Fire Novec1230 Manual - Issue 11 Feb08
Software Program: VdS Schadenverhutung calculation package version 7.3 .
This system is suitable for storage and environmental conditions from -20º to 50º.
System pressure is specified as 25 bar at 2C.