C-7
Catalyst 3750 Switch Hardware Installation Guide
OL-6336-07
Appendix C Connecting to DC Power
Connecting to DC Power
Step 6 Use a ratcheting torque screwdriver to torque the terminal block captive screw (above the installed wire
lead) to 4.5 lbf-in. (72 ozf-in.), as shown in Figure C-8.
Caution Do not overtorque the terminal-block captive screws. The recommended maximum torque is 4.5 lbf-in.
(72 ozf-in.)
Figure C-8 Torquing the Terminal-Block Captive Screws
Step 7
Repeat Steps 4 and 5 for the remaining three DC-input power source wires. Figure C-9 shows the
completed wiring of a terminal block plug.
Figure C-9 Completed Wiring of Terminal Block Plug
60533
Torque to 4.5 lbf-in. (72 ozf-in.)
60534
Return
Negative
Return
Negative
Feed A
Feed B