Rev C Doc 6001288 (01-20285) 16 of 39
I want my gate to move And my gate length is:
This far out at the end: 8’ 10’ 12’
One foot Enter 5” Enter 4” Enter 3”
Two feet Enter 10” Enter 8” Enter 6”
Three feet Enter 15” Enter 12” Enter 9”
N. POST INSTALLATION PROCEDURE
1. Setup
1. Turn on the main power at the gate operator’s circuit breaker.
2. Verify that switch S1 (the Gate Open Direction switch) is set to the correct position.
3. Turn on the Unit power switch.
2. Manual Inputs
1. Verify that Manual Open fully opens the gate and that the open limit switch stops the gate.
2. Verify that Manual Close fully closes the gate and that the close limit switch stops the gate.
3. Verify that Manual Stop stops the gate.
Note: If the gate stops due to a Reverse Fault, readjust the gate sensitivity pots.
3. Mechanical
Use the Manual Input commands to verify that:
1. The gate swings open and closed smoothly.
2. There is no squeak or vibration in the gate when it is moving.
3. There is no belt slippage when the gate moves or stops.
4. Both gates open and close at the same time (Bi-Parting gates only).
4. Gate Sensitivity
1. Left/Right Reverse sensitivity:
Apply a bump to the opening and closing gate and verify that the gate stops or reverses.
2. Inrush (Gate response time):
Apply a bump to the gate as it initiates opening and closing and verify that the gate
responds to the bump within a second.
5. Maximum Retry Count
1. If you want the gate to resume operation automatically after an occurrence of a Fault, program
for Max Retry Count and Retry Pause Time.
2. If you do not want the gate to resume automatically after a Fault, disable Max Retry Count.
3. Give the opening gate a quick bump to generate a fault and verify retry operation.
6. Entry Inputs
1. Activate the CYCLE input (entry system), RADIO input (radio transmitter), and EXIT Loop input
(driving over the exit loop) and verify that they fully open the gate. If Reclose Timer is enabled,
it will close the gate.
2. Activate the FIRE input (fire department switch) and verify that the gate fully opens and then
closes immediately. If Reclose Timer is enable, it will close the gate.