![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/d/e1/de1b33a6-5905-4ceb-ad8e-e40687be389b/de1b33a6-5905-4ceb-ad8e-e40687be389b-bg30.png)
48
13.1.5. Compressor Overheating Prevention Control
• Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of
frequency are as below.
• If compressor discharge temperature exceeds 110qC, compressor will be stopped, occurs 4 times per 20 minutes, timer LED will
be blinking. (“F97” is indicated.)
13.1.6. Low Pressure Prevention Control (Gas Leakage Detection)
a. Control start conditions
• For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
• During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 4qC.
• During Heating operations :
Indoor piping temperature - indoor suction is under 5qC.
b. Control contents
• Compressor stops (and restart after 3 minutes).
• If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated.
13.1.7. Compressor Tank Temperature Rise Protection Control
a. Control start conditions
• For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
• During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 4qC.
Indoor temperature and outdoor temperature is 30±5qC.
Remote Control setting 16qC and Hi Fan Speed.
• During Heating operations:
Indoor piping temperature - indoor suction is under 5qC.
Indoor temperature and outdoor temperature is 20 ± 2qC.
Remote control setting 30qC and Hi Fan Speed.
b. Control contents
• Compressor stops (and restart after 3 minutes)
• If the conditions above happen 2 times within 20 minutes, the unit will:
- Stop operation
- Timer LED blinks and “F91” indicated
13.1.8. Low Frequency Protection Control 1
• When the compressor operate at frequency lower than 24 Hz continued for 20 minutes, the operation frequency will be changed
to 23 Hz for 2 minutes.