White Rodgers 37-5488A Marine Heating System User Manual


 
3
ZONING FOR WATER VALVES
Fig. 4
T1
T2
Z1
Connect Z to 1, T1 to 2, and T2 to 3 on water zone valves
as shown. Refer to sheet packed with water valves for
complete wiring information. For water valves other than
White-Rodgers, consult the valve manufacturer for wiring
details.
ZONING WITH CIRCULATORS
All wiring should be done in accordance with local and national electrical codes and ordinances.
This diagram shows connections for either a line voltage
or 24V Manifold Gas Valve. This diagram may also be
used on Type 668 Kwik-Sensor Oil Burner Controls by
wiring to B1 and B2 terminals as shown on preceding
page.
This diagram is not recommended for normal stack-
mounted oil burner controls because rapid cycling
of the low limit-circulator control may cause the oil
burner control to lock out on safety.
NOTE
12
T1
T2
ZR
ZC
C1 C2
B1 B2B2
Z1
1
42
35
6
T
1
42
35
6
T
T
TT
TYPE 8B43A
RELAY - HOT
WATER CONTROL
ZONE 1
THERMOSTAT
ZONE 2
THERMOSTAT
ZONE 3
THERMOSTAT
TYPE 829A
RELAY
FIELD
INSTALLED
JUMPERS
ZONE 3
CIRCULATOR
ZONE 2
CIRCULATOR
ZONE 1
CIRCULATOR
TRANSF.
24V GAS
VALVE
Fig. 5
Line Voltage
Low Voltage
WIRING
TYPE 829A
RELAY
N
LINE
HOT
CONNECT ADDITIONAL ZONES
AS SHOWN BY DASHED LINES
SERVICING
The temperature control of Type 8B43A controls cannot
be recalibrated in the field, but it can be easily replaced
by removal of two screws. Specify Part No. 77-4387
when ordering replacement.
TERMINAL DESIGNATIONS CROSS REFERENCE
W-R 829A-845 W-R 829A-1 MH R845
1L1
2L2
313
424
535
646
Well No. Description A B C
89-0211 1/2" Std. Shank 1-13/16" 3" 3-5/16"
89-0212 1/2" Std. Ext. Shank 3-5/16" 3" 3-5/16"
89-0213 3/4" Std. Shank 1-13/16" 3" 3-5/16"
89-0214 3/4" Std. Ext. Shank 3-5/16" 3" 3-5/16"
89-0215 3/4" Extra Ext. Shank 4-13/16" 3" 3-5/16"
A
B
C
Fig. 6
TO TERMINALS ON
W-R 1311 OR 1361
ZONE VALVES
3
2
1