Mitsubishi Electronics FR-D720-008 Marine Battery User Manual


 
161
Misoperation prevention and parameter setting restriction
4
PARAMETERS
4.17.2 Parameter write disable selection (Pr. 77)
(1) Write parameters only during stop (setting "0" initial value)
Parameters can be written only during a stop in the PU operation mode.
The shaded parameters in the parameter list (page 56) can always be written regardless of the operation mode and
operating status. However, Pr. 72 PWM frequency selection and Pr. 240 Soft-PWM operation selection can be written when the
inverter is running in the PU operation mode, but cannot be written in the external operation mode.
(2) Inhibit parameter write (setting "1")
(3) Write parameters during operation (setting "2")
Parameters can always be written.
The following prameters cannot be written when the inverter is running even if Pr. 77 = "2". Stop the inverter when changing
their parameter settings.
You can select whether write to various parameters can be performed or not. Use this function to prevent parameter
values from being rewritten by misoperation.
Parameter
Number
Name Initial Value Setting Range Description
77 Parameter write selection
0
0 Write is enabled only during stop.
1 Parameter can not be written.
2
Parameter write is enabled in any operation
mode regardless of operation status.
The above parameter can be set when Pr. 160 Extended function display selection = "0". (Refer to page 162)
Pr. 77 can be always set independently of the operation mode and operation status.
Parameter write is not enabled.
(Read is enabled.)
Parameter clear and all parameter clear cannot be
performed, either.
The parameters given on the right can be written even if Pr.
77 = "1".
Parameter
Number
Name
22 Stall prevention operation level
75
Reset selection/disconnected PU detection/
PU stop selection
77 Parameter write selection
79 Operation mode selection
160 Extended function display selection
296 Password lock level
297 Password lock/unlock
Parameters referred to
Pr. 79 Operation mode selection Refer to page 165
Parameter
Number
Name
23
Stall prevention operation level compensation
factor at double speed
40 RUN key rotation direction selection
48 Second stall prevention operation current
60 Energy saving control selection
66
Stall prevention operation reduction starting
frequency
71 Applied motor
79 Operation mode selection
80 Motor capacity
82 Motor excitation current
83 Rated motor voltage
84 Rated motor frequency
90 Motor constant (R1)
96 Auto tuning setting/status
178 to 182 (input terminal function selection)
190, 192 (output terminal function selection)
255 Life alarm status display
256 Inrush current limit circuit life display
257 Control circuit capacitor life display
258 Main circuit capacitor life display
261 Power failure stop selection
298 Frequency search gain
343 Communication error count
450 Second applied motor
561 PTC thermistor protection level
563 Energization time carrying-over times
564 Operating time carrying-over times
Parameter
Number
Name