White Rodgers 36C Marine Radio User Manual


 
4
PILOT
ADJ.
SLCOM.
BLACK
PRESSURE
SWITCH
TA N
TA N
REDUNDANT
COIL
WHITE
MAIN
RELAY
COIL
TA N
TA N
S
L
COMMON
42
3
Figure 5
Cycle pilot plug-in
Wiring for 36C84-912, -921 & 36C94-906 Gas Valves
24 VAC
LIMIT THERMOSTAT
LINE
TO ELECTRODE
5059 PILOT RELIGHT CONTROL
SILVER
PILOT SOLENOID
COIL
MAIN VALVE RELAY COIL
36C84 GAS VALVE
C
L
3098 MERCURY
FLAME SENSOR
HOT
COLD
COMMON
BRASS
6
2
3
4
5
PRESSURE
SWITCH
N.O.
NOTE: On systems where one side of the low voltage
transformer is grounded, silver terminal (6) of the 5059
must be connected to ground side.
24 VACLINE
THERMOSTATLIMIT
Through
Mounting Hole
To Electrode
5059 PILOT RELIGHT CONTROL
T2
T1
36C87 GAS VALVE
C
L
Main Valve Relay Coil
Pilot Solenoid
Coil
Pressure
Switch
(N.O.)
3098 MERCURY
FLAME SENSOR
Hot
Cold
Common
Plug-In
2
3
4
Figure 6
Wiring for 36C87-944 Gas Valve
INSTALLATION (cont'd)