7
INSTALLATION (cont'd)
1. Attach a manometer to the outlet pressure tap of the
valve.
2. Energize system to ignite main burner.
3. Remove "Reg. Adj." cover screw.
4. To DECREASE outlet pressure, turn the adjusting
screw (beneath the cover screw) counterclockwise.
To INCREASE outlet pressure, turn the adjusting
screw clockwise.
5. Replace the cover screw. Cycle the valve two or three
times to verify regulator setting.
Figure 10
This control was factory preset and will not normally require
additional adjustment of pilot flame.
If the pilot flame is low and does not engulf the bulb of the
sensor, the system will not energize the main valve.
If pilot gas pressure is too high, gas will sputter past the
ignition electrode, and may not ignite. High pilot gas pressure
may also cause the flame to lift off the burner, causing the
flame sensor bulb to sense "low" heat.
To adjust the pilot flame, remove the cover screw and gasket
(see figure 10). To REDUCE pilot flame, turn the pilot adjust
screw (beneath the cover screw) clockwise. To INCREASE
pilot flame, turn the pilot adjust screw counterclockwise.
Replace gasket and tighten cover screw.
PILOT GAS ADJUSTMENT
CONVERSION FROM
NATURAL GAS TO L.P.
1. Remove regulator cover screw.
2. Turn regulator adjustment screw counterclockwise and
remove from valve.
3. Remove regulator spring from valve.
4. Insert proper spring Nat./L.P. into the valve.
5. Replace the regulator adjustment screw and adjust to
appliance manufacturers specifications.
6. Replace regulator cover screw.
OUTLET PRESSURE ADJUSTMENTS
This control is shipped from the factory with the regulator set
to the outlet pressure shown in the table on page 1. Consult
the appliance rating plate to be sure that the setting matches
the appliance manufacturer's specifications. If required, the
regulator can be adjusted for outlet pressures normally
ranging from 2.5 to 5" W.C. (natural gas) or 7.5 to 12" W.C.
(L.P. gas). Do not force the adjusting screw beyond the
limits that it can easily be adjusted.
Conversion Outlet Pressure
from Pilot Gas Regulator
Model Natural/LP Adjustment Adjustment
36C84-912 See Conversion See Fig. 10 See Fig. 10
from Natural Gas
to L.P.
36C84-913 See Conversion See Fig. 10 See Fig. 10
from Natural Gas
to L.P.
36C84-916 Not Convertable See Fig. 10 See Fig. 10
36C84-921 See Conversion See Fig. 10 See Fig. 10
from Natural Gas
to L.P.
36C84-923 Not Convertable See Fig. 10 See Fig. 10
36C84-926 Not Convertable See Fig. 10 See Fig. 10
36C84-936 Not Convertable See Fig. 10 See Fig. 10
36C87-944 Not Convertable See Fig. 10 See Fig. 10
36C94-906 See Conversion See Fig. 10 See Fig. 10
from Natural Gas
to L.P.
36C94-907 See Conversion See Fig. 10 See Fig. 10
from Natural Gas
to L.P.
Pilot Adjust
Cover Screw
Regulator Adjusting
Cover Screw