Diaphragm Metering Pump MEMDOS E - ATE
BW 1 04 02 / 9
Lutz-Jesco GmbH
Improved changes are always reserved without notice.
The operating instructions for the metering
pump and accessories must always be kept
within easy reach.
Contents
1. General
2. Technical data
3. Installation
4. Safety instructions
5. Wiring diagrams
6. Start-up
1. General
The metering pump is installed in accordance with
the applicable operating instructions. The following
description refers exclusively to the electrical ATE
servomotor, types KNG 2.60 and KNG 2.120.
2. Technical data
3. Installation
The ATE servomotor has been mounted on the
pump by the manufacturer and calibrated.
When installing the equipment, a clearance of at
least 150 mm must be allowed for subsequent
maintenance work.
The ATE servomotor must be connected to the
electrical system in accordance with the local
regulations and may only be connected by duly
qualified specialist personnel.
The two basic possibilities for connection are
illustrated in the following wiring diagrams.
Cable type and cross-section must be determined
in accordance with the motor data.
Cable inlets in the housing must be carried out
correctly. We recommend compression glands with
strain relief.
The required degree of protection must be ensured
by correct installation of the electrical connections.
Important:
Please take into account that the ATE drive can only
be controlled with the main motor running, i.e.: the
ATE drive must be locked electrically. Otherwise the
control eccentric may be subject to excessive wear
or damaged.
Pump type Memdos E 4 ... 156 Memdos E 160 ... 380
Servomotor KNG 2.60 KNG 2.60 ST KNG 2.100 KNG 2.120 ST
Part No. 79073 79082 79080 79098
Mechanical design Reversible servomotor with self-locking step-down gear. Connections led out via cables (900 mm).
Angle of rotation limited by two internal limit position switches.
Use For controllers with For controllers with For controllers with For controllers with
switching output (3- continuous output switching output (3- continuous output
point step control). 0/2...10Vor 0/4...20 mA point step control). 0/2...10V or 0/4...20mA
(switchable). (switchable)
Torque 8 Nm 10 Nm
Voltage 230VAC +/-10% 24 VAC +/-10% 230 VAC +/-10% 24 VAC +/-10%
50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Input impedance
at voltage input – 100 kOhm – 100 kOhm
Burden at current input - 500 Ohm - 500 Ohm
Power consumption 4 VA 7.5 VA 4 VA 7.5 VA
Regulating time/bevel 180s (150s) / 270° = 0...100% 360s (300s) / 270° = 0...100%
Load limit of the
voltage output – max. 0.5 A – max. 0.5 A
Position repeating 0...1000 Ohm 0-10 VDC for control 0...1000 Ohm 0-10 VDC for control
signal for remote 2Watt at tu=40°C with 0...10 V and 2Watt at tu=40°C with 0...10 V and
display max. 0...20 mA. 0...20 mA.
2...10 VDC for control 2...10 VDC for control
with 2...10 V and with 2...10 V and
4...20 mA. 4...20 mA.
Type of protection IP 54
Ambient temperature -10 to +60° C
Weight 0.6 kg