18 - 14
18. CNC CONNECTION
18.4 GOT Side Settings
(3) Station number setting switch
(4) Mode setting switch
(1) Switch setting example
For the switch setting example, refer to the
following.
18.5.1 MELSECNET/10 connection
(2) When the switch setting is changed
When changing the switch setting after mounting
the MELSECNET/10 communication unit to the
GOT, reset the GOT.
(3) Self check test
Select "3" to "9" as the mode setting switch to
provide a self check test of the MELSECNET/10
communication unit.
For details, refer to the following manual.
GT15 MELSECNET/10 communication unit
User's Manual
Switch setting (Only when MODEL GT15-
75J61BT13-Z CC-Link communication unit is
used)
Switch setting of the communication unit
When using the MODEL GT15-J61BT13 CC-Link
communication unit, the switch setting is not needed.
For details of each setting switch and LED, refer to the
following manual.
GT15 CC-Link communication unit User's
Manual
(1) Mode setting switch
(2) Station number setting switch
Station number setting
switch
Description Set value
Set the station No. of the
MELSECNET/10
communication unit.
Set to not duplicate other
stations in the network.
(Default: 01)
1 to 64:
GT15-
75J71LP23-Z
1 to 32:
GT15-
75J71BR13-Z
Mode setting switch Description Set value
Online
(Default: 0)
0
5
0
6
1
7
2
8
3
9
4
5
0
6
1
7
2
8
3
9
4
STATION
No.
X10
X1
Mode setting
switch
Description Set value
Select the online mode.
(Default: 0)
0 (fixed)
Station number
setting switch
Description Set value
Specify the station No. of the
CC-Link communication unit.
(Default: 01)
1 to 64
21
ON
4
3
2
1
0
F
E
D
C
B
A
9
8
7
6
5
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
(1)
MODE
STATION NO.
BAUDRATE
SW
1
2
ON
HOLD
4
OFF
CLEAR
1
DA
1357
2468
DG NC NC
DB SLD (FG1) NC
10
1
L ERR.
RD
SD
L RUN
RUN
(4)
(3)
(2)
Left side Front side
GT15-75J61BT13-Z