7-2SectionResponding to Displayed Error Messages
240
Example:
Parity error at serial port A
Receive Errors
The following errors can occur when receiving data.
• Parity error
• Framing error
• Overrun error
• FCS (sum value) error
• Time out error
• Data over flow error
• PC unit No. error (host link only)
• NAK received (in the case of the host link, the end code is also displayed)
• Undefined command error
Send Errors
The following errors can occur when receiving data.
• Time out error
• Data over flow error
The remedies to take in accordance with the displayed cause are indicated in the
table below.
Error Details Displayed Probable Cause Remedy
Parity Error
Framing Error
-
Communication parameters/
conditions set incorrectly.
Check if the settings at the host for parity bit, frame
length, communications speed, stop bit length and
flow control agree with those at the NT31/NT31C.
ver-run
rror
The connecting cables are not
connected correctly.
Check the communication cable connection and
perform a conductivity test. If there is a fault,
replace the cable. For details on communication
cables, refer to Section 4 Connecting to the Host
from the RS-232C Port, and Section 5 Connecting
to the Host from the RS-422A/485 Port.
Noise caused data corruption during
communication.
Carry out grounding work in accordance with the
conditions by referring to 3-1-4 Grounding, page 34.
FCS (Check Sum) Error Noise caused data corruption during
communication.
Carry out grounding work in accordance with the
conditions by referring to 3-1-4 Grounding, page 34.
The PC is transmitting incorrect
data.
Check the operation at the host side.
Probable Causes and
Remedies