“A” Group: Standard Functions
Func.
Code
Name / Description
Default
Value
–FE / –FU /
–FR
Set
Value
A_01 Frequency source setting
00Keypad potentiometer
01Control terminal
02Function F_01 setting
01 / 01 / 00
A_02 Run command source setting
01Input terminal FW or RV (assign-
able)
02Run key on keypad, or digital
operator
01 / 01 / 02
A_03 Base frequency setting 50.0 / 60.0 /
60.0
A_04 Maximum frequency setting 50.0 / 60.0 /
60.0
A_11 O/OI–L input active range start
frequency
0.0
A_12 O/OI–L input active range end frequency 0.0
A_13 O/OI–L input active range start voltage 0
A_14 O/OI–L input active range end voltage 100
A_15 O/OI–L input start frequency enable
00Use A_11 starting value)
01Use 0 Hz
01
A_16 External frequency filter time constant 8
A_20 Multi-speed frequency setting 0
A_21
A_22
A_23
A_24
A_25
A_26
A_27
A_28
A_29..
..A_35
Multi-speed frequency settings 0 / 0 / 5
0 / 0 / 10
0 / 0 / 15
0 / 0 / 20
0 / 0 / 30
0 / 0 / 40
0 / 0 / 50
0 / 0 / 60
0 / 0 / 0
A_38 Jog frequency setting 1.0
A_39 Jog stop mode
00Free-run stop, jogging disabled
during motor run
01Controlled deceleration, jogging
disabled during motor run
02DC braking to stop, jogging
disabled during motor run
00