Mitsubishi Electronics FR-D720S-0.1K to 2.2K Marine Battery User Manual


 
13
Wiring
(2) Total wiring length
The overall wiring length for connection of a single motor or multiple motors should be within the value in the table below.
100V, 200V class
400V class
When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at the motor
terminals, deteriorating the insulation of the motor. Take the following measures 1) or 2) in this case.
1) Use a "400V class inverter-driven insulation-enhanced motor" and set frequency in Pr. 72 PWM frequency selection
according to wiring length
2) Connect the surge voltage suppression filter (FR-ASF-H/FR-BMF-H) on the inverter output side.
2.3.4 Wiring of control circuit
(1) Control circuit terminal layout
Pr. 72 PWM frequency selection Setting
(carrier frequency)
0.1K 0.2K 0.4K 0.75K
1.5K or
higher
1 (1kHz) or less 200m 200m 300m 500m 500m
2 to15
(2kHz to 14.5kHz)
30m 100m 200m 300m 500m
Pr. 72 PWM frequency selection Setting
(carrier frequency)
0.4K 0.75K 1.5K 2.2K
3.7K or
higher
1 (1kHz) or less 200m 200m 300m 500m 500m
2 to15
(2kHz to 14.5kHz)
30m 100m 200m 300m 500m
Wiring Length
50m or less 50m to 100m Exceeding 100m
Carrier frequency
14.5kHz or less 8kHz or less 2kHz or less
NOTE
y Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray
capacitances of the wiring, leading to a malfunction of the overcurrent protective function, fast response current limit
function, or stall prevention function or a malfunction or fault of the equipment connected on the inverter output side.
If malfunction of fast-response current limit function occurs, disable this function. If malfunction of stall prevention
function occurs, increase the stall level. ( Refer to Pr. 22 Stall prevention operation level and Pr. 156 Stall prevention
operation selection in the chapter 4 of the Instruction Manual (applied))
y When using the automatic restart after instantaneous power failure function with wiring length exceeding below,
select without frequency search (Pr. 162 = "1, 11"). (
Refer to Chapter 4 of the Instruction Manual (Applied))
Recommend wire size:
0.3mm
2
to 0.75mm
2
Motor capacity 0.1kW 0.2kW 0.4kW or higher
Wiring length 20m 50m 100m
STF
STR
PCSDRHRMRL
FM
CBA
10 2 5 4
RUN SE S1 S2 SCSO
SD