Omega Engineering OMR-6520 Marine Battery User Manual


 
OMR-6510 3-5
3.2. Setup
Objective of Setup
In normal condition, it only needs to setup the OMR-6510 when the OMR bus with more than 128 modules or
the distance exceeds 4000 feet long. The default configuration of this communication module is 9600 bps and
data format of 8 data bits with 1 start bit, 1 stop bit, and no parity check. Note that the data format is reserved
to be compatible with other brand‘s communication port, it should not be modified if only OMR is used in a
system. The baud rate can be configured according user’s requirement.
Setup Equipments
Only screw driver is used to open the case. Software, power supply, and wiring are not necessary.
Setup Procedure
Only hardware switch setting can be setup in OMR-6510. The user can set the speed and the data format of
the RS-422/RS-485 interface. The speed and the data format on the whole network must be identity otherwise
the communication may be not correct.
To setup the OMR-6510, use the screw driver to open the case, then change the switch setting. The new
setting is available after power on. The case must be put back and locked carefully. Note that do not scratch
the surface of the circuit while setting up, otherwise the surface coating or even the circuits will be damaged.
Default Setting
9600 Baud rate
10 bits serial data format : one start bit, eight data bits, one stop bit, no parity check
SW1 Setting
1 2 3 4 5 6 Baud Rate
ON OFF OFF OFF OFF OFF 1200 or 115.2k
1
bps
OFF ON OFF OFF OFF OFF 2400 bps
OFF OFF ON OFF OFF OFF 4800 bps
OFF OFF OFF ON OFF OFF 9600 bps
OFF OFF OFF OFF ON OFF 19200 bps
OFF OFF OFF OFF OFF ON 38400 bps
Note 1: 115.2kbps is supported by version A1.2 or later.
SW2 Setting