Raritan Engineering PST*03 Marine Sanitation System User Manual


 
5
RECOMMISSIONING\START-UP
Recommissioning
IMPORTANT:
Do not load Tablet Cartridge into Dispenser until system is
powered and operational.
Do Not Operate Purasan until Treatment Unit is filled with
water.
Treatment Tank
1. Reconnect hoses and open seacocks.
2. Reconnect wires and turn power on.
NOTE: Purasan treatment tank must be full before activating a cycle.
IMPORTANT: Do Not connect Tablet Dispenser at this time.
3. Fill the treatment tank:
Single button operation - Remove crossover plug from
Treatment Unit and fill with a minimum of three gallons of
water, replace crossover plug and O-ring.
Independent operation - flush toilet allowing three gallons of
water to pass into Purasan
4. Turn on power to Purasan.
5. Check for leaks.
Reconnecting the Tablet Dispenser
IMPORTANT
• Make sure everything is working properly before proceeding.
• These instructions are the reverse operation outlined in winterizing
the Tablet Dispenser, steps 3 through 6.
1. Remove tube from the bottom of the black “T” fitting and re-
attach to the white “T” fitting or solenoid valve.
2. Reconnect hose on tank to the black “T” fitting on dispenser.
START UP
1. Remove Crossover Cap from treatment unit tower. Pour 3
gallons (11.5 liters) of water into Treatment Unit. Replace
Crossover Cap.
2. Turn on power to unit.
3. Fill toilet bowl half full of water before beginning.
4. Close metering clamp completely, then open slightly.
5. Flush toilet. Check water level in Tablet Dispenser during flush
cycle. Water level should rise to water line marked on Tablet
Dispenser while toilet is flushed, then drain out.
6. Adjust clamp until water reaches the line; opening clamp allows
more water into Tablet Dispenser. Flush toilet each time clamp
adjustment is changed to be sure water continues to be at the
proper level.
7. Load Tablet Cartridge.