PowerLogic
TM
Series 800 Power Meter 63230-500-225A2
Chapter 3—Operation 3/2011
22
PQ Advanced Evaluation Setup
Power Demand Configuration Setup
1. Perform steps 1 through 5 of the SETUP MODE
Access procedure on page 11.
2. Press
###: until ADVAN (advanced setup) is
visible.
3. Press ADVAN.
4. Press
###: until PQADV is visible.
5. Press PQADV.
6. Select ON.
7. Press OK.
8. Change the nominal voltage (NOM V) value if
desired (the default is 230).
9. Press OK to return to the SETUP MODE
screen.
10. At the SETUP MODE screen, continue
programming additional setup features or
press
1; until you are asked to save changes.
11. Press YES to save your changes and reset the
power meter.