2 - Electrical connections
2.3 EXAMPLE OF WIRING DIAGRAM (HEAT COOL CONTROL)
B
Fuse
[5]
6
SupervisorPower supply
RS485
4…20mA
CT Current transformer 50 mA
Fuse
[5]
Power
supply
switch
OP2
OP1
V
~
Fuse 0.2A T
[4]
18V
5
4
3
2
1
12
11
10
9
8
7
0P4
RX/TX
[6]
16
15
Fuse 2A~T
[6]
Alarm
V
~
OP2
18
17
14
13
OP3
[6]
V~
TC
Heating
V~
V~
Cooling
Retransmission
[3]
Notes:
1] Make sure that the power supply
voltage is the same indicated on
the instrument.
2] Switch on the power supply only
after that all the electrical con-
nections have been completed.
3] In accordance with the safety reg-
ulations, the power supply switch
shall bring the identification of the
relevant instrument. The power
supply switch shall be easily
accessible from the operator.
4] The instrument is protected with
a 0.2 A
~ T fuse. In case of fail-
ure it is suggested to return the
instrument to the manufacturer
for repair.
5] To protect the instrument internal
circuits use:
- 2 A
~ T fuses for Relay outputs
- 1 A
~ T fuses for Triac outputs
6] Relay contacts are already pro-
tected with varistors.
Only in case of 24 V ~ induc-
tive loads, use model A51-065-
30D7 varistors (on request)