Hitachi series inverter Marine Battery User Manual


 
13
Error Codes
The L2002 series inverters will trip on over-current, over-voltage, and
under-voltage to protect the inverter. The motor output turns OFF, allow-
ing the motor to free-run to a stop. Press the Stop/Reset key to reset the
inverter and clear the error.
Basic Error Codes
Error
Code
Name Probable Cause(s)
E01
Over current event while at
constant speed
Inverter output was short-circuited
Motor shaft is locked
Load is too heavy
A dual-voltage motor is wired
incorrectly
Note: The L200
2 will over current trip at
nominally 200% of rated current
E02
Over current event during
deceleration
E03
Over current event during
acceleration
E04
Over current event for other
conditions
DC braking power(A054) set too high
Current transformer / noise error
E05
Overload protection Motor overload is detected by the
electronic thermal function
E07
Over voltage protection DC bus voltage exceeds a threshold,
due to regenerative energy from motor
E08
EEPROM error Built-in EEPROM memory experi-
enced noise, high temperature, etc.
E09
Under-voltage error DC bus voltage decreased enough to
cause a control circuit fault
E11
E22
CPU error Built-in CPU had internal error
E12
External trip [EXT] input signal detected
E13
USP (Unattended Start
Protection)
When (USP) was enabled, an error
occurred when power was applied while
a Run signal was present
E14
Ground fault A ground fault was detected between
the inverter output and the motor. This
feature protects the inverter, and does not
protect humans.
E15
Input over-voltage Input voltage was higher than specified
value, after 60 sec. in Stop Mode
E21
Inverter thermal trip Inverter internal temperature is above
the threshold
E30
Driver error Inverter internal error, electrical noise
at CPU-to-drive circuit interface.