![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/6/6a/66afcf06-af77-46e2-b25d-5df69ce9e8bb/66afcf06-af77-46e2-b25d-5df69ce9e8bb-bg19.png)
23
B021/
B221
Overload restriction operation mode
•00Disabled
• 01 Enabled for accel and constant speed
• 02 Enabled for constant speed only
01
B022/
B222
Overload restriction setting Rated
current x 1.5
B023/
B223
Deceleration rate at overload restriction 1.0 / 30.0
B031 Software lock mode selection
• 00 Low-level access, [SFT] blocks edits
• 01 Low-level access, [SFT] blocks edits
(except F001 and Multi-speed parameters)
• 02 No access to edits
• 03 No access to edits except F001 and Multi-
speed parameters
• 03 High-level access, including B031
01
B080 [AM] analog signal gain 100.
B082 Start frequency adjustment 0.5
B083 Carrier frequency setting 5.0
B084 Initialization mode (parameters or trip history)
• 00 Trip history clear
• 01 Parameter initialization
• 02 Trip history clear and parameter
initialization
00
B085 Country code for initialization
• 00 Japan version • 01 Europe version
•02USA version
01 / 02
B086 Frequency scaling conversion factor 1.0
B087 STOP key enable
• 00 Enable • 01 Disable
00
B088 Restart mode after FRS
• 00 Restart from 0Hz
• 01 Restart from frequency detected from
actual speed of motor
00
B089 Monitor display select for networked inverter,
7 options:
• 01 Output frequency monitor
• 02Output current monitor
• 03 Rotation direction monitor
• 04 Process variable (PV), PID feedback
monitor
• 05 Intelligent input terminal status
• 06 Intelligent output terminal status
• 07 Scaled output frequency monitor
01
Func.
Code
Name / Description
Default
Value
–FE(F)/–FU