68
Parameter list
Output terminal
function
116 Third speed detection
0 to 3600r/min 1r/min 1500r/min 95
Communication
functions
117 Commucication station number
0 to 31 1 0 128
118 Communication speed
48, 96, 192 1 192 128
119 Stop bit length/data length
0, 1, 10, 11 1 1 128
120 Parity check presence/absence
0, 1, 2 1 2 128
121 Number of communication retries
0 to 10, 9999 1 1 128
122 Communication check time interval
0 to 999.8s, 9999 0.1s 0 128
123 Waiting time setting
0 to 150ms, 9999 1ms 9999 128
124 CR, LF selection
0, 1, 2 1 1 128
PID control
128 PID action selection
10, 11, 30, 31 1 10 139
129 PID proportional band
0.1 to 1000%,
9999
0.1% 100% 139
130 PID integral time
0.1 to 3600s,
9999
0.1s 1s 139
131 Upper limit
0 to 100%, 9999 0.1% 9999 139
132 Lower limit
0 to 100%, 9999 0.1% 9999 139
133 PID action set point for PU operation
0 to 100% 0.01% 0% 139
134 PID differential time
0.01 to 10s, 9999 0.01s 9999 139
Backlash
140 Backlash acceleration stopping speed
0 to 3600r/min 1r/min 30r/min 89
141 Backlash acceleration stopping time
0 to 360s 0.1s 0.5s 89
142 Backlash deceleration stopping speed
0 to 3600r/min 1r/min 30r/min 89
143 Backlash deceleration stopping time
0 to 360s 0.1s 0.5s 89
Display
functions
144 Speed setting switchover
0, 2, 4, 6, 8, 10 1 0 93
145 Parameter for the option (FR-PU04V)
Current
detection
150 Output current detection level
0 to 200% 0.1% 150% 146
151 Output current detection period
0 to 10s 0.1s 0 146
152 Zero current detection level
0 to 200.0% 0.1% 5.0% 147
153 Zero current detection period
0 to 1s 0.01s 0.5s 147
Sub functions
156 Stall prevention operation selection
0 to 31, 100, 101 1 1 148
157 OL signal output timer
0 to 25s, 9999 0.1s 0 149
Display
functions
158 DA2 terminal function selection
1 to 3, 5 to 12,
17, 18, 21,
32 to 34, 36
1197
160 Extended function selection
0, 1 1 0 150
Automatic
restart after
instantaneous
power failure
162
Automatic restart after instantaneous
power failure selection
0, 1, 10 1 0 101
163 First cushion time for restart
0 to 20s 0.1s 0s 101
164 First cushion voltage for restart
0 to 100% 0.1% 0% 101
165 Restart current limit level
0 to 200% 0.1% 150% 101
Maintenance
functions
168
Maker setting parameters. Do not set.
169
Initial monitor
171 Actual operation hour meter clear
0 1 0 150
Termin al
assignment
functions
180 DI1 terminal function selection
0 to 3, 5, 8 to
12,14 to 16, 20,
22 to 28, 42 to
44, 9999
10
150
181 DI2 terminal function selection
11
182 DI3 terminal function selection
12
183 DI4 terminal function selection
13
187 STR terminal function selection
1 9999
190 DO1 terminal function selection
0 to 8, 10 to 16,
20, 25 to 27, 30
to 37, 39, 40 to
44, 96 to 99, 100
to 108, 110 to
116, 120,125 to
127, 130 to 137,
,139, 140 to 144,
196 to 199, 9999
10
152
191 DO2 terminal function selection
11
192 DO3 terminal function selection
12
195 A,B,C terminal function selection
199
Multi-speed
operation
232 Multi-speed setting (speed 8)
0 to 3600r/min,
9999
1r/min 9999 77
233 Multi-speed setting (speed 9)
0 to 3600r/min,
9999
1r/min 9999 77
234 Multi-speed setting (speed 10)
0 to 3600r/min,
9999
1r/min 9999 77
235 Multi-speed setting (speed 11)
0 to 3600r/min,
9999
1r/min 9999 77
236 Multi-speed setting (speed 12)
0 to 3600r/min,
9999
1r/min 9999 77
Function
Parameter
No.
Name Setting Range
Minimum
Setting
Increments
Factory Setting
Refer
To
Custo
mer
Setting