Mitsumi electronic FR-CV-H37K Marine Radio User Manual


 
45
Standard Specifications
SPECIFICATIONS
4
z 400V class
Type
Heat sink outside mounting
structure
FR-CV-H K
7.511152230
37
(Note 4)
55
(Note 4)
Enclosure inside installation
structure
FR-CV-H K-AT
Applicable inverter
capacity (Note 1)
kW 7.5111522303755
HP 10 15 20 30 40 50 75
Output
Applicable current (A) (Note 1) 17 23 31 43 57 71 110
Regenerative
braking torque
Short-duration
rating
150% torque 60s
Continuous
rating
100% torque
Power supply
Rated input AC voltage,
frequency
Three phase 380 to 480V 50Hz/60Hz
Permissible AC voltage
fluctuation
Three phase 323 to 528V 50Hz/60Hz
Permissible frequency
fluctuation
±5%
Power supply system capacity
(kVA) (Note 2)
17 20 28 41 52 66 100
Protective structure (JEM 1030) Open type (IP00)
Cooling system
Self-
cooling
Forced air cooling
Approximately weight
(kg (lbs))
Heat sink
outside
mounting
structure
6.0
(13.2)
6.0
(13.2)
6.0
(13.2)
10.0
(22.0)
10.0
(22.0)
32.5
(71.7)
32.5
(71.5)
Enclosure
inside
installation
structure
7.5
(16.5)
7.5
(16.5)
7.5
(16.5)
13.0
(28.7)
13.0
(28.7)
Input signal Reset
Output signal Ready output signal, inverter run enable signal, converter reset, alarm signal
Protective functions
Overcurrent protection, overvoltage protection, electronic overcurrent protection,
undervoltage, phase failure, CPU alarm, instantaneous power failure alarm, power
supply alarm
Environment
Ambient temperature -10°C to +50°C (14°F to 122°F) (non-freezing)
Ambient humidity 90%RH or less (non-condensing)
Storage temperature -20°C to 50°C (-4°F to 122°F)
Ambience Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Altitude
Maximum 1000m (3280.80feet) above sea level for standard operation.
After that derate by 3% for every extra 500m (1640.40feet) up to 2500m
(8202.00feet) (91%).
Vibration
5.9m/s
2
or less
Dedicated stand-alone reactor
FR-CVL-
H7.5K
FR-CVL-
H11K
FR-CVL-
H15K
FR-CVL-
H22K
FR-CVL-
H30K
FR-CVL-
H37K
FR-CVL-
H55K