Schneider Electric PM850 Marine Instruments User Manual


 
© 2011 Schneider Electric. All Rights Reserved.
PowerLogic
TM
Series 800 Power Meter 63230-500-225A2
Chapter 3—Operation 3/2011
16
PTs Setup
HZ (System Frequency) Setup
SYS (System Type) Setup
1. Perform steps 1 through 5 of the SETUP MODE
Access procedure on page 11.
2. Press
###: until METER is visible.
3. Press METER.
4. Press PT.
5. Enter the SCALE value: x1, x10, x100, NO PT
(for direct connect).
6. Press OK.
7. Enter the PRIM (primary) value.
8. Press OK.
9. Enter the SEC. (secondary) value.
10. Press OK.
11. At the SETUP MODE screen, continue
programming additional setup features or
press
1; until you are asked to save changes.
12. Press YES to save the changes.

042!4)/
 /+


02)-
3#!,%
3%#
8
PLSD110112
1. Perform steps 1 through 5 of the SETUP MODE
Access procedure on page 11.
2. Press
###: until METER is visible.
3. Press METER.
4. Press
###: until HZ is visible.
5. Press HZ.
6. Select the frequency.
7. Press OK.
8. At the SETUP MODE screen, continue
programming additional setup features or
press
1; until you are asked to save changes.
9. Press YES to save the changes.

3934%-&QDPTD.BX
 /+


(Y
&2%1

PLSD110109
1. Perform steps 1 through 5 of the SETUP MODE
Access procedure on page 11.
2. Press
###: until METER is visible.
3. Press METER.
4. Press ###: until SYS is visible.
5. Press SYS.
6. Select your system (SYS) type (D) based on
the number of wires (A), the number of CTs (B),
and the number of voltage connections (either
direct connect or with PT) (C).
7. Press OK.
8. At the SETUP MODE screen, continue
programming additional setup features or
press
1; until you are asked to save changes.
9. Press YES to save the changes.
0(!3%3934%-


#4
04
393

7)2%
/+
A
B
C
D
PLSD110324