Schneider Electric PM850 Marine Instruments User Manual


 
63230-500-225A2 PowerLogic
TM
Series 800 Power Meter
3/2011 Appendix A—Instrument Transformer Wiring: Troubleshooting Tables
© 2011 Schneider Electric All Rights Reserved
77
Section III—Case E
Symptoms: 4-Wire Possible Causes
kW = near 0
kVA = near 0
3-phase average power factor flip-flopping lead
and lag
Voltages, currents, and kVA are normal
Two CT secondary leads are swapped (A-phase on B-phase terminal, for
example).
Two PT secondary leads are swapped (A-phase on B-phase terminal, for
example).
NOTE: In either case, the phase input that is not swapped will read normal lagging power
factor.
Section III—Case F
Symptoms: 4-Wire Possible Causes
kW = negative and less than kVAR
KVAR = negative and close to value expected
for kW
kVA = expected value
Power factor low and leading
Voltages and currents are normal
All three PT lead connections “rotated” counterclockwise: A-phase wire on
C-phase terminal, B-phase wire on A-phase terminal, C-phase wire on B-
phase terminal.
All three CT lead connections “rotated” clockwise: A-phase wire on B-phase
terminal, B-phase wire on C-phase terminal, C-phase wire on A-phase
terminal.
Section III—Case G
Symptoms: 4-Wire Possible Causes
kW = negative and less than kVAR
kVAR = positive and close to the value for kW
NOTE: looks like kW and kVAR swapped places
kVA = expected value
Power factor low and lagging
Voltages and currents are normal
All three PT lead connections “rotated” clockwise: A-phase wire on B-phase
terminal, B-phase wire on C-phase terminal, C-phase wire on A-phase
terminal.
All three CT lead connections “rotated” counterclockwise: A-phase wire on
C-phase terminal, B-phase wire on A-phase terminal, C-phase wire on B-
phase terminal.