Troubleshooting Reference
975-0376-01-01 4–5
12 N/A No AC output
voltage; there is DC
input voltage
indication.
Inverter fuse open.
GFCI outlet tripped.
The inverter could have
been connected with
reverse DC input
polarity.
Inverter fuses are not
user-replaceable. Return the
inverter. See the Warranty
section for return information.
If AC voltage is present on
one AC outlet but not on the
other, then the GFCI
protection on the outlet may
have tripped. Disconnect all
loads and push the Reset
button on the GFCI outlet.
Reconnect the load to the
receptacle that was tripped,
and if it trips again, the load or
its wiring is faulty and must be
serviced by a qualified service
personnel.
The inverter has been
damaged. Return the inverter.
See the Warranty section for
return information.
NOTE: Damage caused by
reverse polarity is not covered
by the warranty.
Table 4-1
Troubleshooting Reference
#
Error/Warning
Code on Display Problem Possible Cause Solution