36 Freedom HF Owner’s Guide
Warning Messages
 Low battery voltage detected
depending on setting, see
“Operating Limits” on page 22.
Inverting Check battery status and recharge if necessary.
Check for proper DC cable sizing.
Check for loose connections and tighten if necessary.
 AC output overload warning Inverting Reduce the loads connected to the AC outlet of the unit.
 Over-temperature warning Inverting Reduce the loads connected to the AC outlet of the unit.
Check that the ventilation grille is not blocked.
Check for ambient temperature and move the unit to a cooler
location whenever possible.
 not used
 not used
 High battery voltage (> 15.5 V) AC shore power Check for external charging sources, such as an over voltage
alternator, and disconnect if necessary.
Confirm that the external charging source is not the cause. The error
may be caused by the internal battery charger system. Call Xantrex
for support.
 Over-temperature detected on
the AC transfer relay
AC shore power Reduce the loads connected to the AC outlet of the unit.
Check that the ventilation grille is not blocked.
Check for ambient temperature and move the unit to a cooler
location whenever possible.
Table 7
Error Codes Displayed on the Display Panel Screen
Error Code Condition Mode Action