Quick Installation Guide
00825-0100-4716, Rev DA
October 2009
Rosemount 3095 MultiVariable
11
STEP 3 CONTINUED...
Installing the HART Modem
After installing the 3095 Engineering Assistant, the HART modem configuration window
automatically appears when the 3095 Engineering Assistant is opened. If this window is
canceled, the HART modem may be installed manually with the following procedure.
1. Close AMS. From the Start Menu select Programs > 3095 Engineering Assistant >
AMS Network.
2. Select Add from the AMS Network Configuration window. A “Select AMS Network
Component Type” window will open.
3. Select Hart Modem.
4. Select Install.
5. Step through the Wizard. A prompt will inquire a COMM PORT. A typical default is
“COMM 1”.
6. Select OK. Close out of the AMS Network Configuration window.
7. Re-open the HART Modem Properties. Click on the Connection tab and set the Retry
Count to 5. Click the Advanced tab and check the Multidrop checkbox and set the
Address Range as 0 to 2.
8. The configuration change will activate when 3095 Engineering Assistant is launched.
NOTE
Exit from the program if a Palm Pilot HotSync or any other program is shared with the
COMM PORT.
3095 Engineering Assistant (EA) for FOUNDATION Fieldbus
1. Install the 3095 Engineering Assistant for FOUNDATION Fieldbus Program and
the F
OUNDATION fieldbus communication card drivers.
a.Place CD-ROM disk 2 into the drive.
b.Browse and select 3095 Engineering Assistant for F
OUNDATION Fieldbus software
application from Windows NT, 2000, or XP
c.Open the ReadMe.txt file and follow the instructions provided.
2. Install the F
OUNDATION Fieldbus communication card.
a.Insert either the PCMCIA card or PCI card into the computer, following the
instructions provided with the communications card.
3. Connect the 3095 transmitter to computer and establish communications.
a.Connect the 9-pin communications cable into the F
OUNDATION Fieldbus card port
located in the computer.
b.Connect communication wiring to connection ports labeled “D
+
” and “D
-
”.
c.Open the transmitter cover on the side marked “Field Terminals” and connect the
communication wires to the two 3095 transmitter terminals labeled “Fieldbus
Wiring”.
4. Select the 3095 Engineering Assistant for F
OUNDATION Fieldbus from the program menu
or use the 3095 EA F
OUNDATION fieldbus shortcut icon.