Emerson 00825-0100-4716 Marine Instruments User Manual


 
Quick Installation Guide
00825-0100-4716, Rev DA
October 2009
Rosemount 3095 MultiVariable
16
STEP 5: CONFIGURE THE TRANSMITTER (FIELDBUS)
Each FOUNDATION fieldbus host or configuration tool has a different way of displaying and
performing configurations. Some use Device Descriptions (DD) or DD methods for
configuration and to display data consistently across platforms. There is no requirement that
a host or configuration tool support these features.
Use the following block examples to do basic configuration to the transmitter. For more
advanced configurations including configuring the 3095 Mass Flow transducer block, see
the 3095 Manual (00809-0100-4716).
NOTE
DeltaV users should use DeltaV Explorer for the Resource and Transducer blocks and
Control Studio for the Function Blocks.
Send the Configuration to the Transmitter
Use the following steps to create and send the mass flow configuration to the Mass Flow
Transducer Block.
NOTE
All previous Mass Flow transducer block information will be overwritten when the
configuration is sent.
1. Open the 3095 Engineering Assistant for F
OUNDATION fieldbus.
2. Select scan to scan the F
OUNDATION fieldbus segment and select the device requiring
the new or updated mass flow configuration file.
3. Select the EA Wizard.
4. Step through the Flow Configuration Wizard to create a mass flow configuration file.
5. Save the new or updated mass flow configuration file. Files must be saved for future
review or update. Files cannot be uploaded from the Mass Flow Transducer Block.
6. Select send to send the mass flow configuration file to the selected transmitter Mass
Flow Transducer Block.
To configure the AI Block
AI Block configuration parameters
Parameters Enter Data
Channel 1 = Pressure
2 = Static Pressure
3 = Process Temperature
4 = Device Temperature
5 = Mass Flow
L_Type Direct, Indirect, or Square Root
XD_Scale Scale and Engineering Units
(Note: Only select the units that are supported by the device.)
Pressure:
Pa bar inH20 @ 68°F psi inHg @ 0°C
kPa mbar mmH20 @ 68°F g/cm2 mmHg @ 0°C
mPa atm ftH20 @ 68°F kg/cm2 mmH20 @ 4°C
torr inH20 @ 4°C
Temperature:
°C °F K
Mass Flow Rate:
lb
m
/sec lb
m
/min lb
m
/hr lb
m
/day kg/sec
kg/min kg/hour g/sec g/min g/hr
StdCuFt/sec StdCuFt/min
StdCuFt/hr StdCuFt/day StdCuM/sec
StdCuM/min StdCuM/hr StdCuM/day
Out_Scale Scale and Engineering Units