Hitachi SJ700B Marine Battery User Manual


 
= Allowed
= Not permitted
Code Function Name Monitored data or setting
Default Setting
Setting
during
operation
(allowed or not)
Change
during
operation
(allowed or not)
SJ700/SJ700D(CTmode)
SJ700B
-FE -FU -F -F -FU
Intelligent output terminals
C021
Terminal (11) function
00 (RUN: running), 01 (FA1: constant-speed reached), 02 (FA2: set frequency
overreached), 03 (OL: overload notice advance signal (1)), 04 (OD: output
deviation for PID control), 05 (AL: alarm signal), 06 (FA3: set frequency
reached), 07 (OTQ: over-torque), 08 (IP: instantaneous power failure), 09 (UV:
undervoltage), 10 (TRQ: torque limited), 11 (RNT: operation time over), 12 (ONT:
plug-in time over), 13 (THM: thermal alarm signal), 19 (BRK: brake release), 20
(BER: braking error), 21 (ZS: 0 Hz detection signal), 22 (DSE: speed deviation
maximum), 23 (POK: positioning completed),24 (FA4: set frequency overreached
2), 25 (FA5: set frequency reached 2), 26 (OL2: overload notice advance
signal (2)), 27 (Odc: Analog O disconnection detection), 28 (OIDc: Analog OI
disconnection detection), 29 (O2Dc: Analog O2 disconnection detection), 31
(FBV: PID feedback comparison), 32 (NDc: communication line disconnection),
33 (LOG1: logical operation result 1), 34 (LOG2: logical operation result 2),
35 (LOG3: logical operation result 3), 36 (LOG4: logical operation result 4), 37
(LOG5: logical operation result 5), 38 (LOG6: logical operation result 6), 39 (WAC:
capacitor life warning) (*2), 40 (WAF: cooling-fan speed drop), 41 (FR: starting
contact signal), 42 (OHF: heat sink overheat warning), 43 (LOC: low-current
indication signal), 44 (M01: general-purpose output 1), 45 (M02: general-purpose
output 2), 46 (M03: general-purpose output 3), 47 (M04: general-purpose output
4), 48 (M05: general-purpose output 5), 49 (M06: general-purpose output 6),
50 (IRDY: inverter ready), 51 (FWR: forward rotation), 52 (RVR: reverse rotation),
53 (MJA: major failure), 54 (WCO: window comparator O), 55 (WCOI: window
comparator OI), 56 (WCO2: window comparator O2) (When alarm code output
is selected for "C062", functions "AC0" to "AC2" or "AC0" to "AC3" [ACn: alarm
code output] are forcibly assigned to intelligent output terminals 11 to 13 or 11
to 14, respectively.)
01
(FA1)
01
(FA1)
01
(FA1)
01
(FA1)
01
(FA1)
C022
Terminal (12) function
00
(RUN)
00
(RUN)
00
(RUN)
00
(RUN)
00
(RUN)
C023
Terminal (13) function
03
(OL)
03
(OL)
03
(OL)
03
(OL)
03
(OL)
C024
Terminal (14) function
07
(OTO)
07
(OTO)
07
(OTO)
07
(OTO)
07
(OTO)
C025
Terminal (15) function
40
(WAF)
40
(WAF)
40
(WAF)
40
(WAF)
40
(WAF)
C026
Alarm relay terminal function
05
(AL)
05
(AL)
05
(AL)
05
(AL)
05
(AL)
Analog monitoring
C027
FM signal selection
00 (output frequency), 01 (output current), 02 (output torque), 03 (digital
output frequency), 04 (output voltage), 05 (input power), 06 (electronic thermal
overload), 07 (LAD frequency), 08 (digital current monitoring), 09 (motor
temperature), 10 (heat sink temperature), 12 (general-purpose output YA0)
00 00 00 00 00
C028
AM signal selection
00 (output frequency), 01 (output current), 02 (output torque), 04 (output
voltage), 05 (input power), 06 (electronic thermal overload), 07 (LAD frequency),
09 (motor temperature), 10 (heat sink temperature), 11 (output torque [signed
value]), 13 (general-purpose output YA1)
00 00 00 00 00
C029
AMI signal selection
00 (output frequency), 01 (output current), 02 (output torque), 04 (output voltage),
05 (input power), 06 (electronic thermal overload), 07 (LAD frequency), 09 (motor
temperature), 10 (heat sink temperature), 14 (general-purpose output YA2)
00 00 00 00 00
C030
Digital current monitor reference value
SJ700/SJ700D:0.20 x "rated current" to 2.00 x "rated current" (A) / SJ700B:0.20
x "rated current" to 1.50 x "rated current" (A)
(Current with digital current monitor output at 1,440 Hz)
Rated current of
inverter x 1.00
Intelligent
output terminals
C031
Terminal (11) active state
00 (NO) / 01 (NC)
00 00 00 00 00
C032
Terminal (12) active state
00 (NO) / 01 (NC)
00 00 00 00 00
C033
Terminal (13) active state
00 (NO) / 01 (NC)
00 00 00 00 00
C034
Terminal (14) active state
00 (NO) / 01 (NC)
00 00 00 00 00
C035
Terminal (15) active state
00 (NO) / 01 (NC)
00 00 00 00 00
C036
Alarm relay terminal active state
00 (NO) / 01 (NC)
01 01 01 01 01
Levels and output terminal status
C038
Low-current indication signal output mode
selection
00 (output during acceleration/deceleration and constant-speed operation),
01 (output only during constant-speed operation)
01 01 01 01 01
C039
Low-current indication signal detection level
SJ700/SJ700D (CT):0.0 to 2.00 x "rated current" (A)
< 75kW and over:0.0 to 1.80 x "rated current" (A)>
SJ700D (VT)/SJ700B:0.0 to 1.50 x "rated current" (A)
Rated current of inverter x 1.00
C040
Overload signal output mode
00 (output during acceleration/deceleration and constant-speed operation),
01 (output only during constant-speed operation)
01 01 01 01 01
C041
Overload level setting
SJ700/SJ700D (CT):0.0 to 2.00 x "rated current" (A)
< 75kW and over:0.0 to 1.80 x "rated current" (A)>
SJ700D (VT)/SJ700B:0.0 to 1.50 x "rated current" (A)
Rated current of inverter x 1.00
C042
Frequency arrival setting for accel.
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.00 0.00 0.00 0.00 0.00
C043
Frequency arrival setting for decel.
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.00 0.00 0.00 0.00 0.00
C044
PID deviation level setting
0.0 to 100.0 (%)
3.0 3.0 3.0 3.0 3.0
C045
Frequency arrival setting for acceleration (2)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.00 0.00 0.00 0.00 0.00
C046
Frequency arrival setting for deceleration (2)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*1)
0.00 0.00 0.00 0.00 0.00
C052
Maximum PID feedback data
0.0 to 100.0 (%)
100.0 100.0 100.0 100.0 100.0
C053
Minimum PID feedback data
0.0 to 100.0 (%)
0.0 0.0 0.0 0.0 0.0
C055
Over-torque (Forward-driving) level setting
SJ700/SJ700D (CT): 0. to 200. (%) < 75kW and over:0. to 180.>
SJ700D (VT)/SJ700B: 0. to 150. (%)
100. 100. 100. 100. 100.
C056
Over-torque (Reverse-regenerating)
level setting
SJ700/SJ700D (CT): 0. to 200. (%) < 75kW and over:0. to 180.>
SJ700D (VT)/SJ700B: 0. to 150. (%)
100. 100. 100. 100. 100.
C057
Over-torque (Reverse-driving) level setting
SJ700/SJ700D (CT): 0. to 200. (%) < 75kW and over:0. to 180.>
SJ700D (VT)/SJ700B: 0. to 150. (%)
100. 100. 100. 100. 100.
C058
Over-torque (Forward-regenerating)
level setting
SJ700/SJ700D (CT): 0. to 200. (%) < 75kW and over:0. to 180.>
SJ700D (VT)/SJ700B: 0. to 150. (%)
100. 100. 100. 100. 100.
C061
Electronic thermal warning level setting
0. to 100. (%)
80. 80. 80. 80. 80.
C062
Alarm code input
00 (Disabled) / 01 (3-bit) / 02 (4-bit)
00 00 00 00 00
C063
Zero speed detection level
0.00 to 99.99, 100.0 (Hz)
0.00 0.00 0.00 0.00 0.00
C064
Heat sink overheat warning level
0. to 200.0 ()
120. 120. 120. 120. 120.
Communication function
C071
Communication speed selection (*2)
SJ700D: 02 (loopback test), 03 (2,400 bps), 04 (4,800 bps), 05 (9,600 bps),
06 (19,200 bps), 07 (38,400 bps), 08 (57,600 bps), 09 (76,800 bps), 10 (115,200 bps)
SJ700/SJ700B: 02 (loopback test), 03 (2,400 bps), 04 (4,800 bps), 05 (9,600 bps),
06 (19,200 bps)
04 04 04 04 04
C072
Node allocation
SJ700D:
1 to 247,
SJ700/SJ700B:
1 to 32
1. 1. 1. 1. 1.
C073
Communication data length selection
7 (7 bits), 8 (8 bits)
7 7 7 7 7
C074
Communication parity selection
00 (no parity), 01 (even parity), 02 (odd parity)
00 00 00 00 00
C075
Communication stop bit selection
1 (1 bit), 2 (2 bits)
1 1 1 1 1
(*1) 4000HF:0.00 to 99.99, 100.0 to 120.0 (Hz)
20