11. Test run
11.1. The following phenomena do not represent trouble (emergency)
Display of remote controller
“Cooling (heating)” flashes
Normal display
Normal display
Defrost display
No lighting
Heat ready
“HO” or “PLEASE WAIT” flashes
Light out
Cause
When another indoor unit is performing the heating (cooling) operation,
the cooling (heating) operation is not performed.
Because of the control operation of auto vane, it may change over to horizontal
blow automatically from the downward blow in cooling in case the downward
blow operation has been continued for 1 hour. At defrosting in heating, hot adjust-
ing and thermostat OFF, it automatically changes over to horizontal blow.
Ultra-low speed operation is commenced at thermostat OFF.
Light air automatically changes over to set value by time or piping temperature at
thermostat ON.
The fan is to stop during defrosting.
Fan is to run for 1 minute after stopping to exhaust residual heat (only in heating).
Ultra low-speed operation for 5 minutes after SW ON or until piping temperature
becomes 35 °C [95 °F], low speed operation for 2 minutes thereafter, and then
set notch is commenced. (Hot adjust control)
System is being driven.
Operate remote controller again after HO or PLEASE WAIT disappear.
After a stop of cooling operation, unit continues to operate drain pump for three
minutes and then stops it.
Unit continues to operate drain pump if drainage is generated, even during a
stop.
Phenomenon
Indoor unit does not perform cooling (heat-
ing) operation.
The auto vane runs freely.
Fan setting changes during heating.
Fan stops during heating operation.
Fan does not stop while operation has been
stopped.
No setting of fan while start SW has been
turned on.
Indoor unit remote controller shows HO or
PLEASE WAIT indicator for about five min-
utes when turning ON universal power sup-
ply.
Drain pump does not stop while unit has been
stopped.
Drain pump continues to operate while unit
has been stopped.
1. Use a separate power supply for the heat source unit and indoor unit.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10 %.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for heat source use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For
example, use wiring such as YZW.
6. A switch with at least 3.5 mm [0.14 in] contact separation in each pole shall be provided by the Air conditioner installation.
Warning:
Be sure to use specified wires to connect so that no external force is imparted to terminal connections. If connections are not fixed firmly, it may cause
heating or fire.
Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
Caution:
A breaker for current leakage must be attached to the power supply. If no earth leakage breaker is installed, it may cause an electric shock.
Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with too large capacity may cause a malfunction
of unit or fire.
10.4. Wiring of main power supply and equipment capacity
Schematic Drawing of Wiring (Example)
[Fig. 10.4.1] (P.5)
A Switch (breakers for wiring and current leakage) B Breakers for current leakage C Heat source unit
D Pull box E Indoor unit
30
40
15
30
40
15
30
40
15
5.3/10
8.4/8
0.41/22
5.3/10
8.4/8
0.41/22
Main cable
Switch (A)
Minimum wire thickness (mm
2
/AWG)
Branch Capacity Fuse
Heat source unit
BC controller, indoor unit
P72
P96
0.41/22
Breaker for
wiring (NFB)
Ground
30 A 100 mA 0.1sec. or less
40 A 100 mA 0.1sec. or less
20 A 30 mA 0.1sec. or less
Breaker for current leakage
Thickness of wire for main power supply, On/Off capacities and system impedance
12. Information on rating plate
P72
7.0 kg [15 LBS 7 oz]
266 kg [588 LBS]
Model
Refrigerant (R410A)
Allowable pressure (Ps)
Net weight
P96
8.0 kg [17 LBS 11 oz]
269 kg [594 LBS]
MANUFACTURER: MITSUBISHI ELECTRIC CORPORATION AIR-CONDITIONING & REFRIGERATION SYSTEMS
WORKS 5-66, TEBIRA, 6-CHOME, WAKAYAMA CITY, JAPAN
HP: 4.15 MPa [601 psi], LP: 2.21 MPa [320 psi]