Section 3–Installation and Wiring
Sensor Input Wiring
Sensor Wiring Notes
For safety and best controller performance,
Sensor leads (thermocouple and RTD) should not be run in the same
conduit as power wiring.
Twisted pair, shielded wire is recommended for sensor connections.
False temperature readings can occur if the sensor wire is exposed
to electrical noise.
Ungrounded thermocouples are recommended.
Thermocouple extension wire, if required, must be the same type
as the thermocouple (i.e. if a Type K thermocouple is used, then Type
K extension wire must be used.)
Shielded thermocouple wire, if used, must have the shield
grounded at one end only, preferably at the shield ground terminal on
the controller as shown in Figure 3.6.
Three-wire RTDs are recommended for greatest accuracy.
Standard shielded copper wire
is recommended for RTD extensions.
Thermocouple Inputs
It is important to observe polarity (+,-) when connecting thermocouple
leadwires. ANSI color coding for the thermocouples used with this
instrument are
Thermocouple
Type Material Polarity (+) Polarity (-)
J iron/constantan white red
K chromel/alumel yellow red
Make thermocouple wiring connections to terminals as shown in Figure
3.6.
Figure 3.6
Thermocouple Connections with Shield
TC -
NC
NO
COM
TC +
Shield Ground