F002: Unable to locate WESDAC_<x> table
Cause
The DCA was unable to locate one of the required WESDAC data base tables.
Remedy:
Ensure the WESDAC_<x> table exists in the WIN application and is comprised of at least
one record. Refer to the chapter on configuring WIN for more information on configuring
WESDAC points.
F003: Insufficient WESDAC_<x> points, <y> req’d
Cause
There are not enough WESDAC data points allocated to the Serial Status DCA.
Remedy:
Ensure the DCA Index configured in A166APPL refers to the correct WIN CFG_DCA
record.
Refer to the Configuring WIN for the Serial Status DCA chapter, and ensure the required
number of data points are allocated for the Serial Status DCA in the appropriate WIN
System Point Database record. The WESDAC point types are described in the following
table.
WESDAC Name Point Type
WESDAC_1 Digital Inputs
WESDAC_2 Digital Outputs
WESDAC_3 Accumulators
WESDAC_4 Analog Inputs
WESDAC_5 Analog Outputs
WESDAC_6 Devices
Table 4 WESDAC Point Types
F004: Unable to open a channel to WIN
Cause
The DCA was unable to initiate communications with WIN.
Remedy:
Contact the Customer Service Department and report this error.
F005: Not enough memory !!!
Cause
The DCA was unable to allocate enough memory to start the Serial Status DCA.
Remedy:
Reduce the amount of memory used by this or other applications in the system.
Contact the Customer Service Department and report this error.