GE A166-0CG Marine GPS System User Manual


 
GE Energy Services
Serial Status DCA
Configuration Guide
A166-0CG-1.00-2 Restricted
14
Full
E012: <com_port> unable to set timers, status = <x>
Cause
The system was unable to set the communication timers for the specified communication
port.
Effect:
The Serial Status DCA will be unable to communicate over the port, <com_port>.
Remedy:
Note the return status, <x>, and contact the Customer Service Department to report this error.
E013: <com_port> unable to turn RTS on, status = <x>
Cause
The system was unable to turn on RTS for the specified communication port.
Effect:
The Serial Status DCA will not be able to reset the Serial Status Board connected to the port,
<com_port>.
Remedy:
Possible hardware failures:
D20 serial port failure.
Serial Status Board failure.
E100: A166PORT rec <x>, Invalid Baud Rate
Cause
One of the Baud Rates configured in the Port table is not supported by the DCA.
Effect:
The communication port defined by record <x> in A166PORT will not be initialized or used
by the DCA.
Remedy:
Baud rate for the Serial Status DCA must be set at 9600.
E101: A166PORT rec <x>, Invalid Com Failures
Cause
One of the Failures Before Off-line parameters configured in the Port table is too small.
Effect:
The communication port defined by record <x> in A166PORT will not be initialized or used
by the DCA.
Remedy:
Ensure the Failures Before Off-line parameter configured in record <x> of A166PORT is not
zero.