GE A166-0CG Marine GPS System User Manual


 
Serial Status DCA
Configuration Guide
GE Energy Services
Restricted A166-0CG-1.00-2
Full
13
E004: Unable to spawn scan process, rec <x>
Cause
The system encountered an error while trying to spawn one of the scan processes.
Effect:
One of the scan processes will not be started. As a result, the Serial Status DCA will be
unable to communicate over the communication port configured in record <x> of
A166PORT.
Remedy:
Contact the Customer Service Department and report this error.
E005: Com message exchange has been deleted
Cause
One of the communication process message exchanges has been deleted.
Effect:
One of the communication processes will no longer function. As a result, the Serial Status
DCA will be unable to communicate over one of the communication ports.
Remedy:
Contact the Customer Service Department and report this error.
E010:Unable to open <com_port>, status = <x>
Cause
The DCA was unable to open the requested communication port.
Effect:
The Serial Status DCA will be unable to communicate over the specified communication
port, <com_port>
Remedy:
Ensure the specified communication port, <com_port>, is not already used in another record
in A166PORT, or by another application.
Ensure the specified port name is supported by the hardware platform being used. Valid port
names for the D20 are COM0 to COM7. COM0 is normally used for WESMAINT.
E011: <com_port> unable to set parameters, status = <x>
Cause
The system was unable to set the communication parameters for the specified communication
port.
Effect:
The Serial Status DCA will be unable to communicate over the port, <com_port>.
Remedy:
Note the return status, <x>, and contact the Customer Service Department to report this error.