EXTENSION ANALOG OUTPUT
4
4.5 Adjustment Procedure
4.5.1 Setting of analog output signal voltage/current switchover (Pr. 309)
Use Pr. 309 Analog output signal voltage/current switchover to select whether to output the same signal or
different signals from terminal AM0 (voltage output) and terminal AM1(current output).
Pr. 309
Setting
Parameters for Setting
Parameters
for
Adjustment
Description
Terminal
0
(initial
value)
Same select signals are output
from the voltage output terminal
(AM0) and current output
terminal (AM1). The signal set in
Pr. 306 Analog output signal
selection is made valid. (The
setting of Pr. 310 is made invalid.)
AM0
Pr. 306 : Select the output signal.
Pr. 307 : Output signal value for zero analog output
Pr. 308 : Output signal value for maximum analog output
Pr. 323
Pr. 324
C1 (Pr. 901)
AM1
10
AM0
Pr. 306 : Select the output signal.
Pr. 307 : Analog output value for zero output signal
Pr. 308 : Analog output value for maximum output signal
AM1
1
Different select signals are
output from voltage output
terminal (AM0) and current
output terminal (AM1).
AM0
Pr. 310 : Select the output signal.
Pr. 311 : Output signal value for zero analog output
Pr. 312 : Output signal value for maximum analog output
Pr. 323
C0 (Pr. 900)
AM1
Pr. 306 : Select the output signal.
Pr. 307 : Output signal value for zero analog output
Pr. 308 : Output signal value for maximum analog output
Pr. 324
C1 (Pr. 901)
11
AM0
Pr. 310 : Select the output signal.
Pr. 311 : Analog output value for zero output signal
Pr. 312 : Analog output value for maximum output signal
Pr. 323
C0 (Pr. 900)
AM1
Pr. 306 : Select the output signal.
Pr. 307 : Analog output value for zero output signal
Pr. 308 : Analog output value for maximum output signal
Pr. 324
C1 (Pr. 901)
REMARKS
Analog output means voltage (0 to 10 V) and current (0 to 20mA) output from terminal AM0 and AM1, and output
signal means the monitor signal (refer to page 18) set in Pr. 306 and Pr. 310.