E6581090
K-3
11
11.3 Extended parameters
• Input/output parameters
Title
Communication
No.
Function Unit
Minimum setting
unit Panel/
Communication
Adjustment range
Default
setting
User
setting
Reference
0100 Low speed signal
output frequency
Hz 0.1/0.01 0.6- 0.6 6.1.1
0101 Speed-reach setting
frequency
Hz 0.1/0.01 0.0- 0.0 6.1.2
0109 Analog input/logic
input function
selection (VI/S3)
-- 0: Voltage signal input
(0-5 or 10V)
1: Current signal input
(4-20mA)
2: Contact input
0 6.2.1
0110 Always active
function selection
- - 0~40, 49, 54~61 1
(ST)
6.2.2
0111 Input terminal
selection 1 (F)
- - 0~40, 49, 54~61 2
(F)
6.2.3
0112 Input terminal
selection 2 (R)
- - 0~40, 49, 54~61 3
(R)
6.2.3
0113 Input terminal
selection 3 (S1)
- - 0~40, 49, 54~61 6
(SS1)
6.2.3
0114 Input terminal
selection 4 (S2)
- - 0~40, 49, 54~61 7
(SS2)
6.2.3
0115 Input terminal
selection 5 (VI/S3)*5
- - 5-17 8
(SS3)
6.2.3
0127 Sink/Source selection - - 0: Sink 100: Source
1-99,101-200:
Disabled
*2 6.2.5
0130 Output terminal
selection 1
(FM/OUT)*6
- - 0-13 4
(LOW)
6.2.6
0132 Output terminal
selection 3 (FL)
- - 0-13 10
(FL)
6.2.6
0170 Base frequency 2 Hz 0.1/0.01 25-200 *2 6.3.1
0171 Base frequency
voltage 2
V 1/1 50-500 *2 6.3.1
0172 Torque boost 2 % 0.1/0.1 0.0-30.0 *3 6.3.1
0173 Motor thermal
protection level 2
% 1/1 30-100 100 6.3.1
*2: The value is changed according to the set-up parameter condition.
(VFNC1 (S)-□□□□P□-W type)
FH:80, UL80, VL:60, F127:0, F170:60, F171:200, F204:80, F409:200, F417:1710 for VFNC1 (S)-□□□
□P□ type.
*3: Parameter values vary depending on the capacity. Refer to page K-8.
*5: This function is enabled if is set at 2 (logic input).
*6: This function is enabled if (open collector output) is set at 1.